Daikin FTK25BVMB [61/201] Moisture protection function 2

Daikin ATX35BVMB [61/201] Moisture protection function 2
Control Specification SiBE04-302
52 Function and Control
3. The set of a constant
DOA1CG, DOA2CG, DOA3CG, FCG7 and FCG8 have constants for Cooling / Heating
separately and these constants are distinguished with a suffix c/w.
4. Actual constant
DOA : Outdoor air temperature
CGC : Compressor guard for cooling
CGW : Compressor guard for heating
FCG : Frequency guard for compressor protection
Common setting for 25/35 class
3.10 Moisture Protection Function 2
Outline In order to obtain the dependability of the compressor, the compressor must be stopped
according to the conditions of the temperature of the outdoor air and outdoor heat exchanger.
Detail
Operation stop depending on the outdoor air temperature
Compressor operation turns OFF under the conditions that the system is in cooling operation
and outdoor air temperature is below 10°C (FTK(X)S, ATK(X)S series), 0°C (others).
Cooling
FTK(X)S series
ATK(X)S series
FTK(X) series
ATK(X) series
FT(Y)S series
Heating
FTXS series
ATXS series
FTX series
ATX series
FTYS series
DOA1CGC 18°C18°C DOA1CGW 0°C0°C
DOA2CGC 19°C20°C DOA2CGW 2°C2°C
DOA3CGC 0°C14°C DOA3CGW -4°C-4°C
DOA4CGC 1°C16°C DOA4CGW -2°C-2°C
FCG7C 44 Hz 34 Hz FCG7W 37 Hz 48 Hz
FCG8C 54 Hz 34 Hz FCG8W 52 Hz 54 Hz
FCG8
The lower
frequency limit.
Cancelled FCG7 FCG7Cancelled
DOA3CG
DOA4CG
DOA1CG
DOA2CG
Outdoor temperature
(R1044)