Daikin ATXS25BVMB [162/186] Removal of the four way valve

Daikin ATXS25BVMB [162/186] Removal of the four way valve
SiBE12-314 Outdoor Unit
Removal Procedure 153
1.6 Removal of the Four Way Valve
Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Step
Procedure Points
1. Remove the peripheries.
Remove the followings
so as not to be burned
by a gas brazing
machine.
Four way valve coil
Electronic
expansion valve coil
Putty
1
Loosen the screw and
remove the four way
valve coil.
2
Remove the sheet of
putty.
3
Before working,
make sure that the
refrigerant is empty
in the circuit.
Heat up four brazed
parts of the four way
valve and disconnect in
(a)(b)(c)(d) order. (See
the next page also.)
Provide a protective sheet or
a steel plate so that the
brazing flame cannot
influence peripheries.
4
Withdraw the piping
side by pliers.
Be careful so as not to break
pipes by pressing it
excessively by pliers when
withdrawing it.

Содержание