Daikin FTX25JAV1NB [6/29] Specifications

Daikin FTX35JAV1NB [6/29] Specifications
NOMINAL CAPACITY and NOMINAL INPUT
For indoor units only:
INDOOR UNITS FTX25JAV1NB FTX35JAV1NB FTXD50JV1B FTXD60JV1B FTXD71JV1B
NOMINAL INPUT Cooling kW 0.04 0.04 0.04 0.045 0.05
Heating kW 0.04 0.04 0.038 0.045 0.05
For combination indoor units + outdoor units:
INDOOR UNITS FTX25JAV1NB FTX35JAV1NB FTXD50JV1B FTXD60JV1B FTXD71JV1B
OUTDOOR UNITS RX25JV1NB RX35JV1NB RXD50JV1B RXD60JV1B RXD71JV1B
NOMINAL CAPACITY (3-4) Cooling (1) min.nom.max. kW 1.302.503.00 1.403.433.80 0.905.205.80 0.906.207.00 0.907.108.00
Heating (2) min.nom.max. kW 1.303.404.00 1.404.105.10 0.906.508.00 0.907.208.50 0.908.509.50
NOMINAL INPUT Cooling min.nom.max. kW 0.350.981.35 0.501.431.72 0.451.732.30 0.452.212.90 0.452.633.45
Heating min.nom.max. kW 0.351.1301.350 0.4051.3751.90 0.451.912.80 0.452.123.30 0.452.743.80
TECHNICAL SPECIFICATIONS
INDOOR UNITS FTX25JAV1NB FTX35JAV1NB FTXD50JV1B FTXD60JV1B FTXD71JV1B
DIMENSIONS Unit H mm 273 273 298 298 298
W mm 784 784 1,050 1,050 1,050
D mm 185 185 190 190 190
WEIGHT Unit kg 7.5 7.5 12 12 12
COLOUR Unit Almond white
SOUND LEVEL Sound pressure
(cooling/heating) (5)
high dBA 38/38 39/39 44/42 45/44 46/46
medium
dBA 32/32 33/33 40/37 41/39 42/40
low dBA 26/26 27/27 35/32 37/34 37/34
Sound power (Horizontally located scroll type)
(6)
dBA 54/54 55/55 60/58 61/60 62/62
FAN Air flow rate high m
3
/min 7.1/8.4 7.4/8.4 12.3/14.9 13.0/16.5 13.7/17.3
medium
m
3
/min 5.9/7.0 6.0/7.1 10.7/12.8 11.5/13.7 11.8/14.1
low m
3
/min 4.6/5.7 4.7/5.9 9.1/10.5 9.9/11.1 9.9/11.1
Speed steps 5 steps and auto
high rpm 1,260/1,300 1,300/1,300 1,320/1,280 1,380/1,380 1,450/1,450
medium
rpm 1,075/1,125 1,100/1,130 1,170/1,120 1,240/1,190 1,270/1,220
low rpm 890/950 900/970 1,020/960 1,100/1,000 1,100/1,000
Type Cross flow fan
Qty x model 1 x 18F-22 1 x 18F-22 1 x D54A-31
(DC-Motor)
1 x D54A-31
(DC-Motor)
1 x D54A-31
(DC-Motor)
Qty x motor output W 1 x 18 1 x 18 1 x 54 1 x 54 1 x 54
HEAT EXCHANGER Type J7 Hi-XA tube
Rows x stages x fin pitch mm 2 x 12 x 1.4 2 x 12 x 1.4 2 x 14 x 1.2 2 x 14 x 1.2 2 x 14 x 1.2
AIR FILTER Removable/washable/mildew proof
AIR DIRECTION CONTROL Right, left, horizontal and downward
TEMPERATURE CONTROL Microcomputer control
PIPING CONNECTIONS liquid mm J 6.4 J 6.4 J 6.4 J 6.4 J 9.5
gas mm J 9.5 J 12.7 J 12.7 J 15.9 J 15.9
drain mm J 18 J 18 J 18 J 18 J 18
INSULATION MATERIAL Heat insulation tape Both liquid and gas pipes
For outdoor units Pair application See chapter RX(D)-J
Multi model application See chapter MX-H
3D027497B
3D027498B
3D029183/4/5
Wall Mounted Inverter Controlled Unit
R-22
FTK/FTX-JA/FTX-H/FTXD-J
2
Specifications
2
2
4
Split - Sky Air Indoor Units