Daikin RZQ71B7V3B [275/353] Stall prevention time lag l9

Daikin RZQ71B7V3B [275/353] Stall prevention time lag l9
Error Codes: Outdoor Units ESIE04-01
3–76 Part 3 Troubleshooting
3
1
3
4
5
3.17 Stall Prevention (Time Lag) (L9)
Remote Control
Display
L9
Method of
Malfunction
Detection
Malfunction is detected by converting the current flowing to power transistor into voltage with CT1 (DC
current sensor).
Inverter PC board detects the disorder of position signal.
Malfunction
Decision
Conditions
When compressor overload (except for when startup) is detected
When position signal is disordered
Supposed Causes
Faulty compressor (lock)
Pressure differential startup
Faulty inverter
The stop valve is left in closed.