Daikin ARXN50LV1B [6/25] Installation manual
![Daikin ARXN50LV1B [6/25] Installation manual](/views2/1785658/page6/bg6.png)
1-4
! WARNING ! CAUTION
Installation and maintenance should be performed by qualiÞ ed
persons who are familiar with local code and regulation, and
experienced with this type of appliance.
All Þ eld wiring must be installed in accordance with the national
wiring regulation.
Ensure that the rated voltage of the unit corresponds to that of
the name plate before commencing wiring work according to
the wiring diagram.
The unit must be GROUNDED to prevent possible hazard due
to insulation failure.
All electrical wiring must not touch the water piping or any
moving parts of the fan motors.
ConÞ rm that the unit has been switched OFF before installing
or servicing the unit.
Risk of electric shock, can cause injury or death. Disconnect all
remain electric power supplies before servicing.
DO NOT pull out the power cord when the power is ON. This
may cause serious electrical shocks which may result in the
Þ re hazards.
Keep the indoor and outdoor units, power cable and transmission
wiring, at least 1m from TVs and radios, to prevent distorted
pictures and static. {Depending on the type and source of the
electrical waves, static may be heard even when more than
1m away}.
•
•
•
•
•
•
•
•
•
Please take note of the following important points when
installing.
Do not install the unit where leakage of ß ammable gas may
occur.
If gas leaks and accumulates around the unit, it may cause
Þ re ignition.
Ensure that drainage piping is connected properly.
If the drainage piping is not connected properly, it may
cause water leakage which will dampen the furniture.
Do not overcharge the unit.
This unit is factory pre-charged.
Overcharge will cause over-current or damage to the
compressor.
Ensure that the unit’s panel is closed after service or
installation.
Unsecured panels will cause the unit to operate noisily.
Sharp edges and coil surfaces are potential locations which
may cause injury hazards. Avoid from being in contact with
these places.
Before turning off the power supply, set the remote
controller’s ON/OFF switch to the “OFF” position to prevent
the nuisance tripping of the unit. If this is not done, the unit’s
fans will start turning automatically when power resumes, posing
a hazard to service personnel or the user.
Do not install the units at or near doorway.
Do not operate any heating apparatus too close to the air
conditioner unit or use in room where mineral oil, oil vapour
or oil steam exist, this may cause plastic part to melt or
deform as a result of excessive heat or chemical reaction.
When the unit is used in kitchen, keep ß our away from
going
into suction of the unit.
This unit is not suitable for factory used where cutting oil
mist or iron powder exist or voltage ß uctuates greatly.
Do not install the units at area like hot spring or oil reÞ nery
plant where sulphide gas exists.
Ensure the color of wires of the outdoor unit and the terminal
markings are same to the indoors
respectively.
IMPORTANT: DO NOT INSTALL OR USE THE AIR
CONDITIONER UNIT IN A LAUNDRY ROOM.
Don’t use joined and twisted wires for incoming power
supply.
The equipment is not intended for use in a potentially
explosive atmosphere.
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
SAFETY PRECAUTIONS
INSTALLATION MANUAL
NOTICE
Disposal requirements
Your air conditioning product is marked with this symbol. This means that electrical and electronic products shall not be mixed with
unsorted household waste.
Do not try to dismantle the system yourself: the dismantling of the air conditioning system, treatment of the refrigerant, of oil and of
other parts must be done by a qualiÞ ed installer in accordance with relevant local and national legislation.
Air conditioners must be treated at a specialized treatment facility for re-use, recycling and recovery. By ensuring this product is
disposed of correctly, you will help to prevent potential negative consequences for the environment and human health. Please contact
the installer or local authority for more information.
Batteries must be removed from the remote controller and disposed of separately in accordance with relevant local and national
legislation.
This manual provides the procedures of installation to ensure a safe and good standard of operation for the air conditioner unit.
Special adjustment may be necessary to suit local requirement.
Before using your air conditioner, please read this instruction manual carefully and keep it for future reference.
This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial use by lay
persons.
This appliance is not intended for use by persons, including children, with reduced physical, sensory or mental capabilities, or lack of
experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible
for their safety.
Children should be supervised to ensure that they do not play with the appliance.
Содержание
- Arxn25lv1b arxn35lv1b 1
- Arxn50lv1b arxn60lv1b 1
- Atxn25lv1b atxn35lv1b 1
- Atxn50lv1b atxn60lv1b 1
- Deutsch 1
- English 1
- Español 1
- Français 1
- Installation manual 1
- Italiano 1
- Models 1
- R410a split series 1
- Türkçe 1
- Русский 1
- All dimensions are in mm 3
- English 3
- Indoor unit 3
- Outline and dimensions 3
- Outdoor unit arxn25 35lv1b 4
- English 5
- Outdoor unit arxn50 60lv1b 5
- Installation manual 6
- Notice 6
- Safety precautions 6
- Warning caution 6
- English 7
- Important 7
- Important information regarding the refrigerant used 7
- Indoor unit 8
- Installation diagram 8
- Installation of the outdoor unit arxn25 35lv1b 8
- More than 100 8
- More than 150 8
- More than 300 more than 50 8
- More than 50 8
- More than 50 more than 50 8
- Or less 8
- Outdoor unit 8
- Side view 8
- Top view 8
- Unit mm 8
- Wall facing one side 8
- Wall facing three sides 8
- Wall facing two sides 8
- Where a wall or other obstacle is in the path of outdoor unit s intake or exhaust airflow follow the installation guidelines below for any of the below installation patterns the wall height on the exhaust side should be 1200mm or less 8
- Condensed water disposal of outdoor unit heat pump unit only 9
- Drain work heat pump unit only 9
- English 9
- Installation of the outdoor unit arxn50 60lv1b 9
- All dimensions are in mm 10
- Installation of the indoor unit 10
- Left side left back or left bottom piping 10
- Right side right back or right bottom piping 10
- The indoor unit must be installed in such a way so as to prevent short circuit of the cool discharged air with the hot return air please follow the installation clearance shown in the figure do not place the indoor unit where there could be direct sunlight shining on it also this location must be suitable for piping and drainage and be away from doors or windows 10
- The refrigerant piping can be routed to the unit in a number of ways left or right from the back of the unit by using the cut out holes on the casing of the unit bend the pipes carefully to the required position in order to align it with the holes for the side and bottom out hold the bottom of the piping and then position it to the required direction the condensation drain hose can be taped to the pipes 10
- Caution 11
- Do not install the unit at altitude over 2000m for both indoor outdoor 11
- English 11
- Ensure that the wall is strong enough to withstand the weight of the unit otherwise it is necessary to reinforce the wall with plates beams or pillars use the level gauge for horizontal mounting and fix it with 5 suitable screws for atxn25 35lv1b and 7 suitable screws for atxn50 60lv1b in case the rear piping draws out drill a hole 65mm in diameter with a cone drill slightly lower on the outside wall see figure 11
- Hole with cone drill 11
- Hook the claws of the bottom frame to the mounting plate 11
- Hook the indoor unit onto the upper portion of the installation plate engage the two hooks at the rear top of the indoor unit with the upper edge of the installation plate ensure that the hooks are properly seated on the installation plate by moving it to the left and right 11
- How to attach the indoor unit 11
- How to remove the indoor unit 11
- Mount the unit onto the installation plate 11
- Mounting installation plate 11
- Push up the marked area at the lower part of the front grille to release the claws 11
- Recommended mounting plate retention spots and dimensions 11
- The indoor drain pipe must be in a downward gradient for smooth drainage avoid situations that are likely to cause water to leak 11
- Water drainage 11
- Water drainage piping 11
- Additional charge 12
- Additional refrigerant charge g per additional 1m length as tabulated 12
- Allowable piping length 12
- Refrigerant piping 12
- English 13
- Piping connection to the units 13
- Piping works and flaring technique 13
- Refrigerant piping 13
- Electrical wiring connection 14
- Charge operation 15
- English 15
- Special precautions when dealing with r410a unit 15
- Vacuuming and charging 15
- Vacuuming the piping and the indoor unit 15
- Cooling unit heat pump unit 16
- Indicator lights 16
- Ir signal receiver 16
- Led indicator lights for cooling unit heat pump unit 16
- Led indicator lights normal operation and fault conditions for cooling heat pump unit 16
- Cooling heating 17
- Db dry bulb wb wet bulb 17
- English 17
- Indoor temp cdb 17
- Indoor temp cwb 17
- Model atxn25 35lv1b arxn25 35lv1b 17
- Model atxn50 60lv1b arxn50 60lv1b 17
- Operating range 17
- Outdoor temp cdb 17
- Outdoor temp cwb 17
- Air filter 18
- Clean or replace each filter 18
- Open the front panel 18
- Pull out the air filters 18
- Set the air filter and bio filter with bacteriostatic virustatic functions as they were and close the front panel 18
- Take off the bio filter with bacteriostatic virustatic functions 18
- Attach the front panel 19
- Caution 19
- English 19
- Open the front panel 19
- Remove the front panel 19
- Service and maintenance 19
- Caution 20
- For any enquiries on spare part please contact your authorized dealer when any malfunction of the air conditioner unit is noted immediately switch off the power supply to the unit check the following fault conditions and causes for some simple troubleshooting tips 20
- If the fault persists please call your local dealer serviceman 20
- Troubleshooting 20
- When the unit is not to be used for an extended long period of time 20
- Daikin europe n v 22
- En60335 2 40 22
- Ftxn25lv1b ftxn35lv1b ftxn50lv1b ftxn60lv1b atxn25lv1b atxn35lv1b atxn50lv1b atxn60lv1b 22
- Low voltage 2006 95 ec electromagnetic compatibility 2004 108 ec 22
- Pw54723 23m 22
- Shigeki morita vice president ostend 1st of december 2011 22
- Daikin europe n v 23
- En60335 2 40 23
- Low voltage 2006 95 ec machinery 2006 42 ec electromagnetic compatibility 2004 108 ec 23
- Pw54723 25m 23
- Rxn25lv1b rxn35lv1b arxn25lv1b arxn35lv1b 23
- Shigeki morita vice president ostend 1st of december 2011 23
- Daikin europe n v 24
- En60335 2 40 24
- Low voltage 2006 95 ec machinery 2006 42 ec electromagnetic compatibility 2004 108 ec 24
- Pw54723 24m 24
- Rxn50lv1b rxn60lv1b arxn50lv1b arxn60lv1b 24
- Shigeki morita vice president ostend 1st of december 2011 24
Похожие устройства
- Daikin ARXN50LV1B Инструкция по эксплуатации
- Daikin ARXN60LV1B Инструкция по монтажу
- Daikin ARXN60LV1B Инструкция по эксплуатации
- Daikin FT18HEVLK Инструкция по эксплуатации
- Daikin FT24HEVLK Инструкция по эксплуатации
- Daikin FT30HEVLK Инструкция по эксплуатации
- Daikin FTY18HEVLK Инструкция по эксплуатации
- Daikin FTY24HEVLK Инструкция по эксплуатации
- Daikin FTY30HEVLK Инструкция по эксплуатации
- Tefal PU4026F0 Руководство пользователя
- Tefal K13304 Руководство пользователя
- Tefal K1320404 Руководство пользователя
- Tefal TRAVEL MUG K30802 Руководство пользователя
- Tefal OPTISS DECOR BC5122V Руководство пользователя
- Tefal ESSENTIAL BC5304V0 Руководство по безопасности
- Tefal ESSENTIAL BC5304V0 Краткое руководство
- Tefal INGENIO foldable kitchen scale Руководство по безопасности
- Tefal INGENIO foldable kitchen scale Руководство пользователя
- Tefal OPTISS DECOR BC5109V1 Руководство по безопасности
- Tefal OPTISS strawberry BC5003 Руководство по безопасности