Versions - Configurations - Features
13
SMARTBOXY
FUNCTIONAL VERSIONS
SMARTBOXY F
cooling only.
SMARTBOXY
reverse heat pump.
APPLICATION VERSIONS
M Medium crowding - max 30% fresh air
B High crowding up to 60% fresh air
A Very high crowding from 60% to 100% fresh air.
CONFIGURATIONS
MR for recirculation only.
MSV mixing box section inclusive of motorised dampers, air quality sensor and fan (EC plug fan) to expel
exhaust air for up to 50% of the unit’s nominal air ow rate.
MCV 50 mixing box section inclusive of motorised dampers, air quality sensor and fan (EC plug fan) to expel
exhaust air for up to 50% of the unit’s nominal air ow rate.
Functions: air renewal, free-cooling and active thermodynamic recovery up for up to 50% of fresh air
.
MCV 100 mixing box section inclusive of motorised dampers, air quality sensor and fan (EC plug fan) to expel
exhaust air for up to 100% of the unit’s nominal air ow rate.
Functions: air renewal, free-cooling and active thermodynamic recovery up for up to 100% of fresh air
.
ADDITIONAL FEATURES
Condensing gas combustion heating including high-ef-
ciency heat exchanger and new generation premix burner
with continuous modulation of heating capacity: e ciency
up to 106%, hygienic combustion with no carbon monoxi-
de (CO) emissions and very low nitrogen oxide emissions.
Low NOx - Class 5.
Hot water heating with two-row coil made from copper
tubes and aluminium wings, which can be supplemented by
a 2 or 3-way modulating valve.
Electric heating with battery proposed in di erent op-
tions and with regulator for the modulation of thermal/elec-
tric power.
Immersed electrode steam humidi cation with re-
gulation of steam production based on humidity control in
the enviroment
Hot gas reheat using a coil dedicated to the recovery of
condensing heat produced during the cooling operating
cycle.
Constant air ow rate regulator allows the selected air  ow rate to be maintained, even with
variations in the resistance of the air distribution system.
Variable air  ow rate proportional to system and user needs.
SUPPLEMENTARY RECOVERY MODULES M-RP
The recovery modules, proposed in a dual version M-RP and M-RT and integrated into
SMARTBOXY units, allow
energy to be recovered from the exhaust air through a direct heat exchange with fresh air, made by cross- ow
plate heat exchangers (M-RP modules) or rotary type ones (MRT). The residual energy from the exhaust air
outgoing from the recovery module is also transferred to the thermodynamic cycle activated in the
SMARTBOXY
unit, so as to deliver maximum energy recovery and increase the operating range of the unit itself.