Tecnoclima CF-XTRIM 600 [6/16] 200 300 400 500 550 600 700

Tecnoclima CF-XTRIM 600 [6/16] 200 300 400 500 550 600 700
Range CF-XTRIM
6
CFXTRIM GAS HEATING AND THERMODYNAMIC COOLING VERSION
CF-XTRIM U.M. 100 200 300 400 500 550 600 700
Nominal air flow rate m
3
/h 3.500 6.000 7.500 9.700 12.800 17.000 21.000 26.000
Useful static pressure Pa 250
GAS HEATING - HEATING CAPACITY MODULATION
Heating capacity input Max
Min
kW 29,1 58,2 67,6 99,6 118 (*) 118 (*) 165,8 206,8
kW 9,4 9,4 9,4 18,4 20 20 18,4 33,3
Heating capacity output Max
Min
kW 28 56 65 96 114 114 163 204
kW 10 10 10 19 21 21 19 35
Efficiency Max
Min
% 96,1 96,1 96,1 96,4 96,6 96,5 97,5 99,1
% 106,5 106,5 106,5 103,2 105,1 105,1 105,2 106
Total electrical power kW 0,96 1,49 2,14 2,16 3,36 5,56 5,35 7,91
THERMODYNAMIC COOLING 1
Total cooling capacity
Thermodynamic cycle
kW 22,84 34,95 48,00 65,89 92,50 110,63 139,80 171,58
Total cooling capacity kW 22,40 34,37 46,77 64,89 90,37 106,60 136,20 165,36
Sensible cooling capacity
Thermodynamic cycle
kW 17,0 26,2 35,6 47,0 65,0 81,4 102,0 124,0
No. compressors/ Power stages/
No. circuits
- 1/1/1 2/2/1 2/2/1 2/3/1 2/3/1 2/3/1 2/6/2 2/6/2
Gas refrigerant - R410A
Compressors power consumption kW 5,81 8,78 12,68 15,68 22,45 29,20 35,20 47,90
Total power consumption
Nominal conditions
kW 7,43 11,52 16,13 20,95 29,25 38,13 43,66 58,66
EER compressors - 3,93 3,98 3,79 4,20 4,12 3,79 3,97 3,58
EER European standard
EN 14511:2013
- 3,23 3,19 3,04 3,25 3,21 2,90 3,22 2,88
SEER European standard
EN 14825:2016
- 3,41 3,88 3,66 3,78 3,74 3,48 4,32 3,52
SOUND LEVEL
Sound power dB(A) 77 80 80 80 80 82 82 84
1) Cooling operating conditions: external T 35 °C / U.R. 50% - internal T 27 °C / U.R. 47%
*) On request reducible below to 116 kW
Dimensions CF-XTRIM / CF-XTRIM/P
CF-XTRIM
U.M.
100 200 300 400 500 550 600 700
A mm 1.850 2.750 2.750 3.250 3.250 3.250 3.250 3.250
B mm 1.450 1.700 1.700 2.250 2.250 2.250 2.250 2.250
C mm 1.180 1.400 1.400 1.400 1.400 1.500 2.270 2.270
CFXTRIM 600÷700
CFX
TRIM 100÷550
CFXTRIM