SETUP - EHS(X/H)
6
Check off executed action!Startup Checklist
Pos.
Parameter
Description / Explanation
RoCon HP
16.
T-Room 1-3
Setpoint
These parameters affect, in addition to the external temperature,
the heat curve and possibly the room temperature detected by the
room controller EHS157034 (if present and configured), the flow
target temperature for the heating circuit. If these parameters are
set incorrectly, this can strongly affect the operation of the heat
pump in heating mode.
Ch.5.5, Tab.5-7
17.
T-DHW
Setpoint 1
Target value of the warm water temperature. At startup, do not set
below 40°C. After startup, never set below 35°C!
Ch.5.7, Tab.5-9
Tab. 3-1 (2/2)
Tab. 3-2
Setting values for the parameters “BUH s1 power" / “BUH s2 power":
Variables for energy withdrawal for equalization of sensor drift or system adjustment:
Parameter set value
[kW]
Power rating of the installed
electronic heating element [kW]
Removal for heating support through
mixing valve [kW]
1
0
1
2
3
2
3
3
3
4
3
4
5
6
5
6
6
6
7
6
7
8
9
8
9
9
9
10
9
10
11
9
11
.
.
.
.
9
.
.
9
.
.
.
.