7 Installation
Installer reference guide
30
RRLQ011~016CA + RHBH/X11+16CB
ROTEX HPSU low temperature Bi‑bloc
4P384980-1B – 2016.03
(mm)
>150
620
350
(345-355)
M12
a
a Make sure not to cover the drain holes.
INFORMATION
The recommended height of the upper protruding part of
the bolts is 20mm.
20
NOTICE
Fix the outdoor unit to the foundation bolts using nuts with
resin washers (a). If the coating on the fastening area is
stripped off, the nuts rust easily.
a
7.3.4 To install the outdoor unit
M12
7.3.5 To provide drainage
Make sure that condensation water can be evacuated properly.
Install the unit on a base to make sure that there is a proper
drainage in order to avoid ice accumulation.
Prepare a water drainage channel around the foundation to drain
waste water surrounding the unit.
Avoid drain water flowing over the footpath, so that it does not
become slippery in case of ambient freezing temperatures.
If you install the unit on a frame, install a waterproof plate within
150 mm of the bottom side of the unit in order to prevent the
invasion of water in the unit and to avoid the drain water dripping
(see the following illustration).
NOTICE
If drain holes of the outdoor unit are covered by a mounting
base or by floor surface, raise the unit to provide a free
space of more than 150mm under the outdoor unit.
≥150 mm
Drain holes
Model Bottom view (mm)
RRLQ
35
36
61 99
1671
60 159154182
a b
c
d (4×)
a Discharge side
b Drain holes
c Knockout hole (piping intake - downwards route)
d Anchor points
7.3.6 To prevent the outdoor unit from falling
over
In case the unit is installed in places where strong wind can tilt the
unit, take following measure:
1 Prepare 2 cables as indicated in the following illustration (field
supply).
2 Place the 2 cables over the outdoor unit.
3 Insert a rubber sheet between the cables and the outdoor unit
to prevent the cable from scratching the paint (field supply).
4 Attach the cable’s ends. Tighten those ends.