Daikin EBHQ008BAV3 [49/52] Nit specifications

Daikin EBHQ008BAV3 [49/52] Nit specifications
EBHQ006+008BAV3 + EKCBX/H008BAV3
Unit for air to water heat pump system
4PW64602-1A – 09.2010
Installation manual
47
19. UNIT SPECIFICATIONS
Technical specifications
Electrical specifications
(*) European/International Technical Standard setting the limits for voltage
changes, voltage fluctuations and flicker in public low-voltage supply
systems for equipment with rated current 75 A.
(**) European/International Technical Standard setting the limits for harmonic
currents by equipment connected to public low-voltage systems
with input current >16 A and 75 A per phase
(***) System independence
Outdoor unit EBHQ006BAV3 EBHQ008BAV3
Nominal capacity
Cooling
(a)
(a) Only if connected to EKCBX008BAV3
Refer to the Technical Data
Heating
Refer to the Technical Data
Dimensions H x W x D
(mm)
805 x 1190 x 360
Weight
Machine weight
(kg)
95
Operation weight
(kg)
99
Connections
•water inlet/outlet
1" MBSP
(b)
(b) MBSP = Male British Standard Pipe
Field installed waterpiping
Minimum pressure
resistance
(bar)
4
Minimim temperature
resistance
(°C)
65
Recommended diameter
(inch)
1
Refrigerant
•Type
R410A
Charge
(kg)
1.7
Expansion vessel
•Volume
(l)
6
Pre-pressure
(bar)
1
Maximum working pressure
(MWP)
(bar)
3.0
Pump
•Type
water cooled
•No. of speed
3
Nominal ESP
Cooling
(a)
(kPa)
49.7 45.8
Heating
(kPa)
47.2 34.0
Sound level
Sound power cooling
(a)
(dBA)
63 63
Sound pressure cooling
(a)
(dBA)
48 50
Sound power heating
(dBA)
61 62
Sound pressure heating
(dBA)
48 49
Internal water volume
(l)
5.5
Pressure relief valve
water circuit
(bar)
3
Operation range - water side
Heating
(°C)
+15~+50
Cooling
(a)
(°C)
+5~+22
Domestic hot water by heat
pump
(°C)
+25~+80
Operation range - air side
Heating
(°C)
–15~+25
Cooling
(°C)
+10~+43
Domestic hot water by heat
pump
(°C)
–15~+35
Indoor unit EKCBX008BAV3 EKCBH008BAV3
Dimensions H x W x D
(mm)
390 x 412 x 100
Weight
(kg)
6
Outdoor unit EBHQ006BAV3 EBHQ008BAV3
Power circuit
Phase
1~
•Frequency
(Hz)
50
•Voltage
(V)
230 (±10%)
Maximum running current
(a)
(a) Equipment complying with EN/IEC 61000-3-12 (**)
Cooling
(b)
(b) Only if connected to EKCBX008BAV3
(A)
16.25
Heating
(A)
18
Indoor unit EKCBX008BAV3 EKCBH008BAV3
Power supply
(a)
(a) Above mentioned power supply is for the booster heater (EKW* option) and
backup heater kit (EKMBUH).
The switch box of the EKCB indoor unit is supplied via the outdoor unit.
The EKMBUH heater kit can be installed as a single step 3 kW heater or a 2 step
6 kW heater, for detailed information, refer to the heater kit installation manual.
Phase
1~
•Frequency
(Hz)
50
•Voltage
(V)
230 (±10%)
Running current (heater kit)
(A)
26
•Z
max
(heater kit + booster
heater (EKHWS* models))
(Ohm)
0.29
Running current (heater kit +
booster heater (EKHWS* models)
EK*V3
(A)
39 (26 + 13)
EK*Z2
(A)
33.5
Minimum S
SC
value
(b)
(b) In accordance with EN/IEC 61000-3-11 (*), it may be necessary to consult the
distribution network operator to ensure that the equipment is connected only to a
supply with Z
sys
(***) Z
max
EK*V3
(kVA)
(c)
(c) Equipment complying with EN/IEC 61000-3-12 (**)
EK*Z2
(kVA)
(c)
Operation range
Ambient temperature
(°C)
5~35