Unit for air to water heat pump system
4P348533-1A – 2013.04
Installation manual
18
11.8. Requirements for indoor unit field wiring
Selection and sizing should be done in accordance with the
applicable legislation based on the information in the table below:
11.9. Routing
The indoor unit has several openings on the bottom side for field
wiring. Use the appropriate opening to route the high voltage, low
voltage and power supply wires as shown in the figure below.
11.10.Indoor switch box connections
Connection of control signals and thermistor cable
1 Indoor unit control signals
2 Indoor unit pump and heater control signals
3 Thermistor interconnection cable
In case the EKCBX/H008BCV3 control box is to
be connected to a EBHQ00*BAV3 unit, there is no
need to purchase the obligatory EKCOMCAB1
thermistor interconnection cable option. Refer to
figure 1 for procedure on how to recuperate the
thermistor interconnection cable that originally was
supplied with the EBHQ00*BAV3 unit.
4 In case no EKHW* option with booster heater is
installed, connect an extra ground wire to the
ground terminal.
5 Normal kWh rate power supply
1 Remove the control box cover.
2 Using the appropriate cables, route and connect the control
cables to the appropriate terminals as shown on the wiring
diagram supplied with the unit and according to the figure above.
3 Route and connect the thermistor interconnection cable to the
appropriate terminal as shown on the wiring diagram supplied
with the unit and according to the figure above.
4 Route the cables through the cable holders and secure the
cables to the cable tie mountings with cable ties as shown in the
figure above.
5 Close the control box cover. Take care not to pinch any wires.
Connection heater kit signals (if applicable)
Refer to the installation manual of the EKMBUH heater kit.
Item
Cable
bundle
(a)
(a) PS = Power supply
HV = High voltage
LV = Low voltage
Desciption
Required
number of
conductors
Maximum
running
current
1 HV Indoor unit control signals 3 + GND Minimum
cable section
2.5 mm
2
2 HV Indoor unit pump and
heater control signals
4 1.25 A
(b)
(b) Minimum cable section = 0.75 mm
2
3 LV Thermistor
interconnection cable
(obligatory option
EKCOMCAB1)
8 Obligatory
option
EKCOMCAB
1
4 HV Heater kit control signals
(only for EKMBUH)
5
(b)
5 LV Heater kit R12T
thermistor (only for
EKMBUH)
2
(b)
6 HV Alarm output (only for
EKRP1HB* and
EKSOLHWAV1 option)
2
(b)
7 HV Cooling/heating on/off
output (only for
EKRP1HB* and
EKSOLHWAV1 option)
2
(b)
8 HV Solar input (only for
EKRP1HB*and
EKSOLHWAV1 option)
2
(b)
9 LV Changeover to boiler
output (only for
EKRP1HB* and
EKSOLHWAV1 option)
2
(b)
10 HV 2-way valve (only for
EKCBX* units)
2
(b)
11 HV Room thermostat (only for
EKRTW, EKRTR1 or
EKRTETS option)
1, 3, 4 or 5
(b)
12 LV user interface mounted on
indoor unit front panel
(b)
LV user interface mounted
apart from indoor unit
2
(c)
(c) Cable section 0.75 mm
2
till 1.25 mm
2
, maximum length: 50 m
13 HV 3-way valve (only for
EKHW option)
3
(b)
14 HV Solar pump and thermal
protector (only for
EKSOLHWAV1 option)
2
(b)
15 LV R5T Tank thermistor (only
for EKHW option)
2
16 HV Booster heater power
supply and thermal
protector (only for EKHW
option)
4 + GND
(d)
(d) Refer to the nameplate of the domestic hot water tank
17 HV Domestic hot water tank
thermal protector (only for
EKHWSU option)
2
(b)
18 PS Booster heater power
supply (only for EKHW
option)
2 + GND
(d)
19 PS Normal kWh rate power
supply
2 + GND
(e)
(e) Cable section = 2.5 mm
2
WARNING
It is important to keep the high voltage, low voltage and
power supply wiring separated from each other. In order to
avoid any electrical interference the distance between both
wiring should always be at least 25 mm.
PS/HV HV LV
PS Power supply
HV High voltage
LV Low voltage