Daikin RXYQ30PYNKE [20/24] English
![Daikin RXYQ30PYNKE [20/24] English](/views2/1790733/page20/bg14.png)
16 English
• After H2P stop blinking (about 12 minutes after turning on the
power), check H2P is OFF.
If H2P is ON, check the malfunction code in the remote control-
ler of indoor unit and correct the malfunction in accordance with
[Remote controller display malfunction code] in chapter 11-2.
(3) Check the LED. And push the MODE button (BS1) once if the LED
displays is not as below.
(4) Push the TEST button (BS4) once. (The LED displays will change
as below.)
(5) Hold the TEST button (BS4) down for 5 seconds or more.
(The LED displays will change as below and fan of outdoor unit
will start rotation.)
(6) When the compressor start working and the LED displays change
any state in below (*3), go to “In case of cooling mode” or “In case
of heating mode” in accordance with the LED displays.
In case of cooling mode
(7) Push the TEST button (BS4) once within 5 minutes after proce-
dure (5) (*4) and close the all front panels (*5).
After that, open the valve A immediately (See figure 32) (*6) and
watch the remote controller display of indoor unit.
(8) If the remote controller display shows “PE” code (*7), ready to
close the valve A.
And go to procedure (9).
If the remote controller display shows other code, close the valve
A immediately and refer to [Remote controller cooling mode mal-
function code]
Beware the fan running when open the front panel.
The fan may continue rotation after the system stop the operation.
(9) When the compressor stop working (the fan may continue rota-
tion.), close the valve A immediately (*8).
And check the LED displays are as below and the remote control-
ler display shows “P9” code.
After checking, push the MODE button (BS1) once and the charg-
ing is complete.
In case of heating mode
(7) Push the TEST button (BS4) once within 5 minutes after proce-
dure (5) (*4) and close the all front panels.
After that, open the valve A immediately (See figure 32) (*6) and
check the charged amount by meauring device.
During operation, if the remote controller display shows “P2” or
“P8” code, close the valve A immediately and refer to [Remote
controller heating mode malfunction code].
Beware the fan running when open the front panel.
The fan may continue rotation after the system stop the operation.
(8) When the required amount of refrigerant is charged, close the
valve A (See figure 32) (*8) and push the RETURN button (BS3)
once. And then go to procedure (9).
(9) Push the MODE button (BS1) once, and the charging is complete.
Notes (*1)~(*8)
(*1)
Lead the refrigerant charge hose etc from the pipe intake.
All front panels must be closed at the procedure (7).
(*2)
• If you perform the refrigerant charging operation within the
refrigerant system that have the power off unit, the operation
cannot finish properly.
Check the number of outdoor and indoor units that is powered.
For checking, see [How to check how many units are con-
nected] in chapter 11-1.
• To energize the crankcase heater, make sure to turn on for
6 hours before starting operation.
(*3) It takes about 2~10 minutes for getting stability of refrigerant state.
If the additional refrigerant is little and operation is started before
getting stability, the system can not judge the charging amount
precisely and it cause over charge.
(*4) If the TEST button (BS4) is not pushed within 5 minutes, “P2” code
will displayed in the remote controller. In this case, refer [Remote
controller cooling (or heating) mode malfunction code].
(*5) If the front panel is opened during the operation, the system can-
not operate properly.
(*6) If you leave the system without connecting the refrigerant tank or
opening the valve A for 30 minutes or more, the system stop oper-
ation and “P2” code are displayed in remote controller.
In this case, refer [Remote controller cooling (or heating) mode
malfunction code].
(*7) Depending on the situation of operation such as the charging
amount is little, the “PE” code may not be displayed and the “P9”
code may be displayed.
(*8) Always close the valve A and take the tank off.
The refrigerant charge port of this unit have electric expansion
valve and the valve are closed when charging is finished. However,
the valve will opened when ather operation (Check operation,
nomal operation, etc.). If you leave the tank connected, the refrig-
erant will charged and it cause over charge.
[Remote controller cooling mode malfunction code]
[Remote controller heating mode malfunction code]
Automatic refrigerant charging operation must be carried out at or
below 43°CDB of outside temperature.
If the outside temperature exceeds 43°CDB, follow the directions
below to charge additional refrigerant.
H1P H2P H3P H4P H5P H6P H7P
hhihhhh
H1P H2P H3P H4P H5P H6P H7P
iiiiiii
H1P H2P H3P H4P H5P H6P H7P
hjhhh ∗∗
H1P H2P H3P H4P H5P H6P H7P
jjjhihi
Go to “In case of
cooling mode”
jjh hihi
Go to “In case of
heating mode”
H1P H2P H3P H4P H5P H6P H7P
ijjiiii
Code The work contents
PE Charging is almost finished. Ready to close the valve A.
PA
PH
The refrigerant tank is empty. Close the valve A and
replace empty tank to the new tank. After changing the
tank, open the valve A again.
Beware the fan running. The outdoor unit does not
stop operation.
P8
Close the valve A immediately, and restart the operation
from procedure (3).
P2
Operation is interrupted. Close the
valve A immedeately and check the
below items.
• Check if suction gas pipe or
liquid pipe shutoff valve is
opened.
• Check the refrigerant tank is
connected and the valve A
was opend.
• Check if the air inlet and outlet
of the indoor unit are not
closed by an obstruction.
After correcting the
abnormality, restart
the operation from
procedure (3).
∗
Operation is stoped abnormally.
Close the valve A immediately. Con-
firm the malfunction code and cor-
rect the abnormality following the
[Remote controller displays mal-
function code] in chapter 11-2.
P9
Charging is finished. Close the valve A and take the refrig-
erant tank off.
Code The work contents
P8
Close the valve A immediately and push the TEST button
(BS4) once. And restart from procedure (7) of “In case of
heating mode”.
P2
Operation is interrupted. Close the valve A immedeately
and check the below items.
• Check if suction gas pipe or liquid pipe shutoff valve
is opened.
• Check the refrigerant tank is connected and the valve
A was opend.
• Check if the air inlet and outlet of the indoor unit are
not closed by an obstruction.
01_EN_3P226891-7A.fm Page 16 Tuesday, June 3, 2008 2:35 PM
Содержание
- Installation manual 1
- System air conditioner 1
- Figure 1 2
- Figure 10 figure 11 figure 12 figure 13 2
- Figure 14 2
- Figure 15 2
- Figure 2 2
- Figure 3 2
- Figure 4 2
- Figure 5 2
- Figure 6 2
- Figure 7 2
- Figure 8 2
- Figure 9 2
- Figure 16 3
- Figure 17 3
- Figure 18 3
- Figure 19 figure 20 3
- Figure 21 3
- Figure 22 3
- Figure 23 3
- Figure 24 3
- Figure 25 3
- Figure 26 3
- Figure 27 4
- Figure 28 4
- Figure 29 figure 30 4
- Figure 31 figure 32 4
- Figure 33 4
- Figure 34 4
- Figure 35 4
- 1 safety precautions 5
- Contents 5
- English 1 5
- First of all 5
- Installation manual 5
- 1 combination 6
- 2 special notice of product 6
- 3 disposal requirements 6
- English 6
- Introduction 6
- 2 standard supplied accessories 7
- 3 option accessory 7
- 4 technical and electrical specifications 7
- 5 main components 7
- 6 installation process 7
- English 3 7
- Selection of location 7
- 1 selection of piping material and refrigerant branching kit 8
- English 8
- Inspecting and handling the unit 8
- Placing the unit 8
- Refrigerant piping 8
- 2 protection against contamination when installing pipes 9
- 3 pipe connection 9
- 4 connecting the refrigerant piping 9
- A b 25 9
- Cutting location 9
- English 5 9
- Gas side accessory pipe 2 9
- Gas side piping field supply 9
- Change as shown in the figure below rising height 200 mm or more 10
- Change to pattern 1 or pattern 2 10
- English 10
- Front connections 10
- If 2 m or more 10
- If less than 2m 10
- Less than 2m 10
- M or more 10
- Oil remains in the stopping outdoor unit 10
- Outdoor unit gas pipe 10
- Pattern 1 10
- Pattern 2 10
- Prohibited pattern 10
- To indoor unit 10
- Unit a 10
- Unit b 10
- English 7 11
- 5 example of connection 12
- English 12
- Example of connection 12
- Example refrigerant branch using refnet header 12
- Example refrigerant branch using refnet joint 12
- Pipe size selection 12
- Refrigerant branch kit selection 12
- _en_3p226891 7a fm page 8 tuesday june 3 2008 2 35 pm 12
- Diameter of above case 13
- English 9 13
- How to calculate the additional refrigerant to be charged 13
- Note 1 13
- Note 2 13
- Note 3 13
- 1 power circuit safety device and cable requirements 14
- 2 wiring connection example for whole system 14
- A power circuit see the following table must be provided for con nection of the unit this circuit must be protected with the required safety devices i e a main switch a slow blow fuse on each phase and an earth leakage circuit breaker when using residual current operated circuit breakers be sure to use a high speed type 1 second or less 200ma rated residual operating current use copper conductors only use insulated wire for the power cord select the power supply cable type and size in accordance with relevant local and national regulations 14
- All field wiring and components must be installed by a licensed electrician and must comply with relevant local and national reg ulations be sure to use a dedicated power circuit never use a power sup ply shared by another appliance 14
- Caution 14
- English 14
- Ex combining the rxyq30ptlk e using rxyq8ptlk e rxyq10ptlk e and rxyq12ptlk e 14
- Field wiring 14
- Minimum circuit amp of rxyq10ptlk e in table above 41 a minimum circuit amp of rxyq12ptlk e in table above 41 a accordingly the minimum circuit amp of the rxyq30ptlk e 32 41 41 115 a multiplying the result above by 1 115 1 127 a so the recommended fuse capacity would be 130 a 14
- Note electrical wiring must be done in accordance with the wiring dia grams and the description herein do not operate until refrigerant piping work is completed if operated before complete the piping work the compressor may be broken down never remove thermistor sensor or etc when connecting power wiring and transmission wiring if operated with thermistor sensor or etc removed the compres sor may be broken down this product have reversed phase protection detector that only works when the power is turned on if there exists black out or the power goes on and off which the product is operating attach a reversed phase protection circuit locally running the product in reversed phase may break the compressor and other parts attach the power wire securely introducing power with a missing n phase or with a mistaken n phase will break the unit never connect the power supply in reversed phase the unit can not operate normally in reversed phase if you connect in reversed phase replace two of the 14
- Note make sure the weak electric wiring i e for the remote control ler between units etc and the power wiring do not pass near each other keeping them at least 50 mm apart proximity may cause electrical interference malfunctions and breakage be sure to connect the power wiring to the power wiring termi nal block and secure it as described in 7 5 power wiring connection procedure 14
- Note the above table indicates power specifications for standard combi nations see 2 introduction if using anything other than the above combinations in a multi sys tem calculate using the following procedure minimum circuit amp value add the minimum circuit amp values for each independent unit 14
- Only proceed with wiring work after blocking off all power always ground wires in accordance with relevant local and national regulations this machine includes an inverter device connect earth and leave charge to eliminate the impact on other devices by reducing noise generated from the inverter device and to prevent leaked current from being charged in the outer hull of the product do not connect the ground wire to gas pipes sewage pipes light ning rods or telephone ground wires gas pipes can explode or catch fire if there is a gas leak sewage pipes no grounding effect is possible if hard plastic pip ing is used telephone ground wires and lightning rods dangerous when struck by lightning due to abnormal rise in electrical potential in the grounding be sure to install an earth leakage circuit breaker this unit uses an inverter so install the earth leakage circuit breaker that be capable of handling high harmonics in order to prevent malfunctioning of the earth leakage circuit breaker i 14
- Refer to figure 19 1 power supply 2 main switch 3 earth leakage circuit breaker 4 fuse 5 outdoor unit 6 cool heat selector 7 remote controller 8 indoor unit 14
- Specifications for local wiring are in compliance with iec60245 use wire type h05vv when protected pipes are used use wire type h07rn f when protected pipes are not used 14
- 3 leading wire procedure 15
- 4 transmission wiring connection procedure 15
- 5 power wiring connection procedure 15
- English 11 15
- 1 preparations 16
- 6 procedure for wiring inside units 16
- Air tight test and vacuum dry ing 16
- Air tight test and vacuum drying 16
- Crimp style terminal 16
- Cup washer 16
- Cut out section 16
- English 16
- Power wire crimp style terminal 16
- Resin hook 16
- Terminal block crip style terminal wire narrow wire thick 16
- 1 before working 17
- 2 air tight test and vacuum drying method 17
- Additional refrigerant charge and check operation 17
- Checking of device and instal lation conditions 17
- Checking of device and installation conditions 17
- English 13 17
- Pipe insulation 17
- English 18
- H h i h h h h 18
- J h h h h h h 18
- J h h h i h i 18
- J h h i h h h 18
- J h j h j j h 18
- 2 procedure of adding refrigerant charging and check operation 19
- Cooling mode 19
- English 15 19
- Heating mode 19
- Outdoor temp 0 c db 43 c db indoor temp 10 c db 32 c db less than above range 19
- English 20
- H h i h h h h 20
- H j h h h 20
- I i i i i i i 20
- I j j i i i i 20
- J j h h i h i 20
- J j j h i h i 20
- English 17 21
- J h h h h h h h h 21
- J h h h h h h h j 21
- J h h i h h h h h 21
- J h h i h h h h i 21
- 1 before test run 22
- 1 onsite settings with the power off 22
- 2 onsite settings with the power on 22
- 2 test run 22
- 3 checks after test run 22
- Caution for refrigerant leaks 22
- English 22
- Onsite settings 22
- Test run 22
- English 19 23
Похожие устройства
- Daikin RXYQ32PTLK Инструкция по эксплуатации
- Daikin RXYQ32PTLK Инструкция по монтажу
- Daikin RXYQ32PTLKE Инструкция по эксплуатации
- Daikin RXYQ32PTLKE Инструкция по монтажу
- Daikin RXYQ32PYNK Инструкция по эксплуатации
- Daikin RXYQ32PYNK Инструкция по монтажу
- Daikin RXYQ32PYNKE Инструкция по эксплуатации
- Daikin RXYQ32PYNKE Инструкция по монтажу
- Daikin RXYQ34PTLK Инструкция по эксплуатации
- Daikin RXYQ34PTLK Инструкция по монтажу
- Daikin RXYQ34PTLKE Инструкция по эксплуатации
- Daikin RXYQ34PTLKE Инструкция по монтажу
- Daikin RXYQ34PYNK Инструкция по монтажу
- Daikin RXYQ34PYNK Инструкция по эксплуатации
- Daikin RXYQ34PYNKE Инструкция по эксплуатации
- Daikin RXYQ34PYNKE Инструкция по монтажу
- Daikin RXYQ36PTLK Инструкция по эксплуатации
- Daikin RXYQ36PTLK Инструкция по монтажу
- Daikin RXYQ36PTLKE Инструкция по эксплуатации
- Daikin RXYQ36PTLKE Инструкция по монтажу