Daikin RXYTQ10U7YF [23/44] Piping installation

Daikin RXYTQ8U7YF [23/44] Piping installation
14 Piping installation
Installation and operation manual
23
RXYTQ8~16U7YF
VRV IV+ heat pump for high ambient temperatures
4P546223-1B – 2020.10
14.4.4 To charge refrigerant: Flow chart
For more information, see "To charge refrigerant"[424].
Pre-charging refrigerant
Step 1
Calculate additional refrigerant charge amount: R (kg)
Refrigerant overcharge happened, recover
refrigerant to reach R=Q
Step 2
Open valves C and B to the liquid line
Execute pre-charging amount: Q (kg)
Step 3a
Close valves C and B
Charging is finished
Fill in the amount on the additional
refrigerant charge label
Go to test run
Step 3b
Close valves C and B
R=Q R>QR<Q
Continued on next page >>
p
<
p
>
R410AN2
C
A B