10.3 Error codes: Overview
In case other error codes appear, contact your dealer.
Main code Sub code Cause Solution
Master Slave 1 Slave 2
Earth leakage detector activated Restart the unit. If the problem
reoccurs, contact your dealer.
Earth leakage detector malfunction:
open circuit) - A1P (X101A)
Check connection on PCB or actuator.
High pressure switch was activated
(S1PH, S2PH) - A1P (X2A , X3A)
Check stop valve situation or
abnormalities in (field) piping or airflow
over air cooled coil.
Refrigerant overcharge
Stop valve closed
Check refrigerant amount+recharge
unit.
Open stop valves
Stop valve closed (liquid) Open liquid stop valve.
Refrigerant overcharge
Stop valve closed
Check refrigerant amount+recharge
unit.
Open stop valves.
Low pressure malfunction:
Stop valve closed
Refrigerant shortage
Indoor unit malfunction
Open stop valves.
Check refrigerant amount+recharge
unit.
Check the user interface's display or
transmission wiring between the
outdoor unit and the indoor unit.
Electronic expansion valve malfunction
(main) (Y1E) - A1P (X21A)
Check connection on PCB or actuator.
Electronic expansion valve malfunction
(liquid cooling) (Y3E) - A1P (X23A)
Check connection on PCB or actuator.
Electronic expansion valve malfunction
(subcool) (Y2E) - A1P (X22A)
Check connection on PCB or actuator
Electronic expansion valve malfunction
(storage vessel) (Y4E) - A1P (X25A)
Check connection on PCB or actuator
Discharge temperature too high
(R21T/R22T):
Stop valve closed
Refrigerant shortage
Open stop valves.
Check refrigerant amount+recharge
unit.
Compressor casing temperature too
high (R8T/R9T):
Stop valve closed
Refrigerant shortage
Open stop valves.
Check refrigerant amount+recharge
unit.
Refrigerant overcharge
Stop valve closed
Check refrigerant amount+recharge
unit.
Open stop valves.
Ambient temperature sensor
malfunction (R1T) - A1P (X18A)
Check connection on PCB or actuator.