Daikin RZAG140L7V1B [18/40] Installation
![Daikin RZAG140L7V1B [18/40] Installation](/views2/1794866/page18/bg12.png)
6 Installation
Installer reference guide
18
RZAG71~140L7V1B
Split system air conditioners
4P418663-1 – 2016.02
WARNING
▪ Do NOT pierce or burn refrigerant cycle parts.
▪ Do NOT use cleaning materials or means to accelerate
the defrosting process other than those recommended
by the manufacturer.
▪ Be aware that the refrigerant inside the system is
odourless.
WARNING
The refrigerant inside the unit is mildly flammable, but
normally does not leak. If the refrigerant leaks in the room
and comes in contact with fire from a burner, a heater, or a
cooker, this may result in fire, or the formation of a harmful
gas.
Turn off any combustible heating devices, ventilate the
room, and contact the dealer from which you purchased
the unit.
Do not use the unit until a service person confirms that the
portion from which the refrigerant leaked is repaired.
6.6.3 Precautions when charging refrigerant
INFORMATION
Also read the precautions and requirements in the
following chapters:
▪ General safety precautions
▪ Preparation
6.6.4 To determine the additional refrigerant
amount
To determine if adding additional refrigerant is necessary
If Then
L1≤30m (chargeless length) You do not have to add
additional refrigerant.
L1>30m You must add additional
refrigerant.
For future servicing, encircle the
selected amount in the table
below.
INFORMATION
Piping length is the one way length of liquid piping.
To determine the additional refrigerant amount
(additional refrigerant amount in kg)
RZAG
L1 (m)
≤30m ≤40m ≤50m ≤55m ≤60m ≤75m ≤85m
71 0.00 0.35 0.70 0.90 —
100~140 0.00 0.35 0.70 1.05 1.40 1.90
6.6.5 To determine the complete recharge
amount
(complete recharge amount in kg)
RZAG
L1 (m)
≤30m ≤40m ≤50m ≤55m ≤60m ≤75m ≤85m
71 2.60 2.95 3.30 3.50 —
100~140 3.40 3.75 4.10 4.45 4.80 5.30
6.6.6 Charging refrigerant: Setup
See "6.5.3Checking refrigerant piping: Setup"on page16.
6.6.7 To charge refrigerant
WARNING
▪ Only use R32 as refrigerant. Other substances may
cause explosions and accidents.
▪ R32 contains fluorinated greenhouse gases. Its global
warming potential (GWP) value is 675. Do NOT vent
these gases into the atmosphere.
▪ When charging refrigerant, always use protective
gloves and safety glasses.
CAUTION
To avoid compressor breakdown, do NOT charge more
than the specified amount of refrigerant.
Prerequisite: Before charging refrigerant, make sure the refrigerant
piping is connected and checked (leak test and vacuum drying).
1 Connect the refrigerant cylinder to both the service port of the
gas stop valve and the service port of the liquid stop valve.
2 Charge the additional refrigerant amount.
3 Open the stop valves.
If pump down is needed in case of dismantling or relocating the
system, see "11.3To pump down"on page24 for more details.
6.6.8 To fix the fluorinated greenhouse gases
label
1 Fill in the label as follows:
b
Contains fluorinated greenhouse gases
2
1
1
1
2
2
kg
tCO
2
eq
GWP × kg
1000
=
=
+
kg
=
kg
=
GWP: XXX
RXXX
a
f
c
d
e
a If a multilingual fluorinated greenhouse gases label is
delivered with the unit (see accessories), peel off the
applicable language and stick it on top of a.
b Factory refrigerant charge: see unit name plate
c Additional refrigerant amount charged
d Total refrigerant charge
e Greenhouse gas emissions of the total refrigerant charge
expressed as tonnes CO
2
-equivalent
f GWP = Global warming potential
NOTICE
In Europe, the greenhouse gas emissions of the total
refrigerant charge in the system (expressed as tonnes
CO
2
-equivalent) is used to determine the maintenance
intervals. Follow the applicable legislation.
Formula to calculate the greenhouse gas emissions:
GWP value of the refrigerant × Total refrigerant charge [in
kg] / 1000
2 Fix the label on the inside of the outdoor unit. There is a
dedicated place for it on the wiring diagram label.
Содержание
- Installer reference guide 1
- Split system air conditioners 1
- About the box 6 2
- About the documentation 2
- About the documentation 5 2
- About the units and options 7 2
- Commissioning 21 2
- Disposal 23 2
- General safety precautions 2
- General safety precautions 2 2
- Glossary 38 2
- Hand over to the user 23 2
- Installation 10 2
- Installer reference guide 2
- Languages are translations 2
- Maintenance and service 23 2
- Preparation 7 2
- Table of contents 2
- Technical data 25 2
- The original documentation is written in english all other 2
- The precautions described in this document cover very important 2
- Topics follow them carefully 2
- Troubleshooting 23 2
- For the installer 3
- General 3
- General safety precautions 3
- Installation site 3
- Meaning of warnings and symbols 3
- Refrigerant 3
- General safety precautions 4
- About the documentation 5
- About this document 5
- Electrical 5
- About the box 6
- Installer reference guide at a glance 6
- Outdoor unit 6
- Overview about the box 6
- To handle the outdoor unit 6
- To remove the accessories from the outdoor unit 6
- To unpack the outdoor unit 6
- About the units and options 7
- Combining units and options 7
- Identification 7
- Identification label outdoor unit 7
- Installation site requirements of the outdoor unit 7
- Overview about the units and options 7
- Overview preparation 7
- Possible options for the outdoor unit 7
- Preparation 7
- Preparing installation site 7
- Preparation 8
- About the minimum floor area 9
- Additional installation site requirements of the outdoor unit in cold climates 9
- Preparation 9
- To determine the minimum floor area 9
- Wall mounted uni 9
- About preparing electrical wiring 10
- Installation 10
- Overview installation 10
- Preparing electrical wiring 10
- Preparing refrigerant piping 10
- Refrigerant piping diameter 10
- Refrigerant piping insulation 10
- Refrigerant piping length and height difference 10
- Refrigerant piping material 10
- Refrigerant piping requirements 10
- About mounting the outdoor unit 11
- About opening the units 11
- Installation 11
- Mounting the outdoor unit 11
- Opening the units 11
- Precautions when mounting the outdoor unit 11
- To install the outdoor unit 11
- To open the outdoor unit 11
- To provide drainage 11
- To provide the installation structure 11
- About connecting the refrigerant piping 12
- Connecting the refrigerant piping 12
- Installation 12
- Precautions when connecting the refrigerant piping 12
- To prevent the outdoor unit from falling over 12
- Ø6 mm 12
- Guidelines when connecting the refrigerant piping 13
- Installation 13
- Pipe bending guidelines 13
- To braze the pipe end 13
- To flare the pipe end 13
- A b c d e 14
- Installation 14
- To connect the refrigerant piping to the outdoor unit 14
- To handle the service cap 14
- To handle the stem cap 14
- To handle the stop valve 14
- To open close the stop valve 14
- Using the stop valve and service port 14
- B a 4 ø6 mm 15
- Installation 15
- To determine if oil traps are required 15
- About checking the refrigerant piping 16
- Checking refrigerant piping setup 16
- Checking the refrigerant piping 16
- Installation 16
- Precautions when checking the refrigerant piping 16
- To check for leaks 16
- To perform vacuum drying 16
- About charging refrigerant 17
- About the refrigerant 17
- Charging refrigerant 17
- Installation 17
- Charging refrigerant setup 18
- Installation 18
- Precautions when charging refrigerant 18
- To charge refrigerant 18
- To determine the additional refrigerant amount 18
- To determine the complete recharge amount 18
- To fix the fluorinated greenhouse gases label 18
- About connecting the electrical wiring 19
- About electrical compliance 19
- Connecting the electrical wiring 19
- Guidelines when connecting the electrical wiring 19
- Installation 19
- Precautions when connecting the electrical wiring 19
- Specifications of standard wiring components 19
- To connect the electrical wiring on the outdoor unit 19
- A b c d e 20
- Finishing the outdoor unit installation 20
- Installation 20
- To close the outdoor unit 20
- To finish the outdoor unit installation 20
- Checklist before commissioning 21
- Commissioning 21
- Overview commissioning 21
- Precautions when commissioning 21
- To check the insulation resistance of the compressor 21
- Commissioning 22
- Error codes when performing a test run 22
- To perform a test run 22
- Checklist for yearly maintenance of the outdoor unit 23
- Disposal 23
- Hand over to the user 23
- Maintenance and service 23
- Maintenance safety precautions 23
- Overview disposal 23
- Overview maintenance and service 23
- Overview troubleshooting 23
- Precautions when troubleshooting 23
- Troubleshooting 23
- About pump down 24
- Disposal 24
- To pump down 24
- Components 25
- D103893 25
- Dimensions 25
- Dimensions outdoor unit 25
- Latest information can be found in the technical engineering data 25
- Overview technical data 25
- Piping diagram 25
- Rzag71 dimensions in mm 25
- Service space 25
- Technical data 25
- Technical specifications 25
- This chapter contains information about 25
- Wiring diagram 25
- A gas pipe connection ø15 flare connection 26
- B liquid pipe connection ø9 flare connection 26
- C internal service port in the unit 26
- D earthing terminal m5 in the switch box 26
- D103894 26
- E refrigerant piping intake 26
- F power supply wiring intake knockout hole ø34 26
- G control wiring intake knockout hole ø27 26
- H drain hole 26
- I anchor point bolt 4 m12 26
- Installer reference guide 26
- P418663 1 2016 2 26
- Rzag100 140 dimensions in mm 26
- Rzag71 140l7v1b 26
- Split system air conditioners 26
- Technical data 26
- Discharge side take refrigerant piping work into account when positioning the units if your layout does not match any of the layouts below contact your dealer 27
- Service space outdoor unit 27
- Single unit single row of units 27
- Suction side in the illustrations below the service space at the suction side is based on 35 c db and cooling operation forsee more space in the following cases 27
- Technical data 27
- When the heat load of the outdoor units is expected to regularly exceed the maximum operating capacity 27
- When the suction side temperature regularly exceeds this temperature 27
- Multiple rows of units 28
- Stacked units max 2 levels 28
- Technical data 28
- Components outdoor unit 29
- Rzag71 29
- S1ph a d s1pl y2s 29
- S1ph m 29
- Technical data 29
- Rzag100 140 30
- S1pl s1ph m s1ph a 30
- Technical data 30
- Piping diagram outdoor unit 31
- Technical data 31
- 240 v 1n 50 hz 32
- Blk black 32
- Blu blue 32
- Brn brown 32
- Colours 32
- Colours see below 32
- Connection 32
- Connector 32
- D099152 1 32
- Field wiring 32
- Grn green 32
- L live 32
- N l l n 32
- N neutral 32
- Noiseless earth 32
- Option 32
- Ppl purple 32
- Protective earth 32
- Red red 32
- Refer to the combination table and the option manual for how to connect the wiring to x6a x28a and x77a 32
- Refer to the service manual for instructions on how to set the selector switches ds1 the factory setting of all switches is off 32
- Refer to the wiring diagram sticker on the back of the service cover for how to use the bs1 bs4 and ds1 switches 32
- See note 7 32
- Symbols 32
- Symbols see below 32
- Technical data 32
- Terminal 32
- Terminal strip 32
- The wiring diagram is delivered with the unit located at the inside of the service cover rzag71 32
- This wiring diagram applies only to the outdoor unit 32
- When operating do not short circuit protective devices s1ph and s1pl 32
- Wht white 32
- Wiring diagram outdoor unit 32
- Ylw yellow 32
- Technical data 33
- 240 v 1n 50 hz 34
- A1p printed circuit board main 34
- A2p printed circuit board 34
- Blk black 34
- Blu blue 34
- Brn brown 34
- Bs1 bs4 push button switch 34
- C1 c3 capacitor 34
- Colours 34
- Colours see below 34
- Connection 34
- Connector 34
- D099153 1 34
- Ds1 dip switch 34
- E1h bottom plate heater option 34
- Field wiring 34
- Grn green 34
- L live 34
- Legend for wiring diagram rzag100 140 34
- N neutral 34
- Noiseless earth 34
- Option 34
- Ppl purple 34
- Protective earth 34
- Red red 34
- Refer to the combination table and the option manual for how to connect the wiring to x6a x28a and x77a 34
- Refer to the service manual for instructions on how to set the selector switches ds1 the factory setting of all switches is off 34
- Refer to the wiring diagram sticker on the back of the service cover for how to use the bs1 bs4 and ds1 switches 34
- Rzag100 140 34
- Symbols 34
- Symbols see below 34
- Technical data 34
- Terminal 34
- Terminal strip 34
- This wiring diagram applies only to the outdoor unit 34
- When operating do not short circuit protective devices s1ph and s1pl 34
- Wht white 34
- Ylw yellow 34
- Technical data 35
- Technical data 36
- Technical specifications outdoor unit 36
- Technical data 37
- Glossary 38
Похожие устройства
- Alpine INE-F904D Руководство пользователя
- Alpine INE-F904D Инструкция по эксплуатации
- Alpine X903D-F Инструкция по эксплуатации
- Alpine X903D-F Руководство пользователя
- Alpine X703D-F Инструкция по эксплуатации
- Alpine X703D-F Руководство пользователя
- Alpine INE-W611D Инструкция по эксплуатации
- Alpine INE-W611D Руководство пользователя
- Alpine iLX-W650BT Руководство пользователя
- Alpine iLX-W650BT Инструкция по эксплуатации
- Alpine CDE-W296BT 4x50Вт Руководство пользователя
- Daikin RZQ71D7V1B Инструкция по монтажу
- Daikin RZQ71D2V1B Инструкция по монтажу
- Daikin RZQ100D7V1B Инструкция по монтажу
- Daikin RZQ125D7V1B Инструкция по монтажу
- Daikin RZQ140D7V1B Инструкция по монтажу
- Daikin RZQ200B8W1B Инструкция по монтажу
- Daikin RZQ200B8W1B Технические данные
- Daikin RZQ250B8W1B Инструкция по монтажу
- Daikin RZQ250B8W1B Технические данные