Split Sky Air • Outdoor Units
21
Outdoor Units • R410A • RZQ-B
5 Capacity tables
5 - 3 Heating capacity tables
RZQ100B8V3B (Pair + Twin/triple)
Heating
Heating capacity 230V [50Hz]
Indoor Outdoor temp. (°CWB)
EDB 15 10 50 610
(°C)
TC
(kW)
CPI
(-)
TC
(kW)
CPI
(-)
TC
(kW)
CPI
(-)
TC
(kW)
CPI
(-)
TC
(kW)
CPI
(-)
TC
(kW)
CPI
(-)
16.O 7.16 1.01 7.91 1.07 8.66 1.12 9.41 1.17 11.2 0.92 12.1 0.97
18.O 7.15 1.05 7.90 1.11 8.65 1.16 9.39 1.22 11.2 0.96 12.1 1.01
20.0 7.15 1.09 7.89 1.15 8.64 1.21 9.38 1.27 11.2 1.00 12.1 1.05
21.O 7.14 1.12 7.89 1.17 8.63 1.23 9.38 1.29 11.2 1.02 12.1 1.07
22.O 7.14 1.14 7.88 1.20 8.63 1.26 9.37 1.32 11.2 1.04 12.0 1.09
24.0 7.13 1.18 7.87 1.24 8.62 1.30 9.36 1.36 11.2 1.08 12.0 1.13
3D048603
SYMBOLS
AFR: Air flow rate (m
3
/min)
BF: Bypass factor
EWB: Entering wet bulb temp. (°CWB)
EDB: Entering dry bulb temp. (°CDB)
TC: Total cooling/heating capacity (kW)
SHC: Sensible heating capacity (kW)
PI: Power input (kW)
(comp.+indoor+outdoor fan motor)
CPI: Coefficient of power input. (-)
Caution:
TC and SHC are shown by kW
NOTES
1.
Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark j show the max. at standard conditions.
On the figure the mark Q show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
3. On the tables Q show rated capacity and rated coefficient of power input.
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.02 x AFR (m
3
/min.) x (1BF) x (DB*EDB)
AddSHC*toSHC.
5. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is CDB/6° CWB (heating)
Corresponding refrigerant piping length : 7.5 m
Level difference : 0 m
6. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
7. The value contains less than 5% error acording to indoor unit type.
8. Heating capacity include the drop of frost formation.
9. Air flow rate and BF are tabulated below.
Pair
Model FCQ100D FCQ100B FBQ100 FHQ100 FAQ100 FUQ100
AFR
(BF)
30
(0.11)
28
(0.16)
27
(0.20)
24
(0.14)
23
(0.10)
29
(0.07)
Twin
Model FCQ50Bx2 FFQ50x2 FBQ50x2 FHQ50x2
AFR
(BF)
15x2
(0.16x2)
12x2
(0.16x2)
14x2
(0.15x2)
13x2
(0.1x2)
10. Rated power input of each model is tabulated below.
Pair
Model FCQ100D FCQ100B FBQ100 FHQ100 FAQ100 FUQ100
Cooling 2.44 2.64 2.86 3.15 2.78 3.12
Heating 2.56 3.14 3.00 3.60 3.39 3.28
Twin
Model FCQ50Bx2 FFQ50x2 FBQ50x2 FHQ50x2
Cooling 2.78 2.79 3.01 3.32
Heating 3.31 3.21 3.16 3.79
Capacity range
Rated point
Heating capacity
Coefficient of power input. (-)
Triple
Model FCQ35Bx3 FFQ35x3 FBQ35x3 FHQ35x3
AFR
(BF)
14x3
(0.16x3)
10x3
(0.25x3)
11.5x3
(0.15x3)
13x3
(0.2x3)
Triple
Model FCQ35Bx3 FFQ35x3 FBQ35x3 FHQ35x3
Cooling 2.78 2.79 3.01 3.32
Heating 3.31 3.21 3.16 3.79