17
EKHBRD011~016ADV1+Y1
Indoor unit for air to water heat pump system and options
4P402192-1A 2015.04
Field settings table
First
code
Second
code
Setting name
Installer setting at variance with default value
Default
value
Range Step UnitDate Value Date Value
0 Remote control setup
00 Installation related setting 2 2~3 1
01 Installation related setting 0 5~5 0.5 °C
02 Not applicable. Do not change the default value. 1 (ON) ——
03 Status: space heating schedule timer mode 1 (ON) 0/1 ——
1 Automatic storage timing for domestic water heating
00 Status: night time storage 1 (ON) 0/1 ——
01 Night time storage start time 1:00 0:00~23:00 1:00 hour
02 Status: day time storage 0 (OFF) 0/1 ——
03 Day time storage start time 15:00 0:00~23:00 1:00 hour
2 Automatic setback function
00 Status: setback operation 1 (ON) 0/1 ——
01 Setback operation start time 23:00 0:00~23:00 1:00 hour
02 Setback operation stop time 5:00 0:00~23:00 1:00 hour
3 Weather dependent set point
00 Low ambient temperature (Lo_A) 10 20~5 1 °C
01 High ambient temperature (Hi_A) 15 10~20 1 °C
02 Set point at low ambient temperature (Lo_Ti) 70 25~80 1 °C
03 Set point at high ambient temperature (Hi_Ti) 45 25~80 1 °C
4 Disinfection function
00 Status: disinfection operation 1 (ON) 0/1 ——
01 Disinfection operation day selection Fri Mon~Sun ——
02 Disinfection operation start time 23:00 0:00~23:00 1:00 hour
5 Automatic setback and disinfection set point
00 Set point: disinfection operation temperature 70 60~75 5 °C
01 Disinfection operation time duration 10 5~60 5 min
02 Leaving water setback temperature 5 0~10 1 °C
03 Room setback temperature 18 17~23 1 °C
6 Option setup
00 Installation related setting 0 (OFF) 0/1 ——
01 Installation related setting 0 (OFF) 0/1 ——
02 Installation related setting 0 (OFF) 0/1 ——
03 Installation related setting 0 (OFF) 0/1 ——
04 Installation related setting 0 0/2 1
7 Option setup
00 Installation related setting 1 (ON) 0/1 ——
01 Not applicable. Do not change the default value. 0 (OFF) ——
02 Installation related setting 0 (A) 0/1 ——
03 Installation related setting 0 (OFF) 0/1 ——
04 Installation related setting 0 (OFF) 0/1 ——
8 Option setup
00 Installation related setting 1 (ON) 0/1 ——
01 Installation related setting 1 (ON) 0/1 ——
02 Emergency mode 0 (OFF) 0/1 ——
03 Status: low noise level 1 1~3 1
04 Installation related setting 0 0~2 1