Addendum to installation manual
1
EKHBRD011~016ADV1+Y1
4P402187-1B – 2015.09
CONTENTS Page
General information........................................................................... 1
Combination ...................................................................................... 1
Connecting to a benefit kWh rate power supply................................ 1
Connecting to an EMRQ outdoor unit ............................................... 1
Field settings ............................................................................................ 1
Field piping............................................................................................... 1
Capacity index to be allocated to EKHBRD*AD unit ................................ 1
Field settings table ............................................................................ 2
The original instructions are written in English. All other languages
are translations of the original instructions.
General information
Thank you for purchasing this unit.
This unit is a special unit of the EKBRD series: EKHBRD*AD. This
unit can also be connected to an EMRQ outdoor unit. For general
installation and operation, the supplied installation and operation
manuals must be used.
Some additional attention points are explained in this addendum.
They are specific for the EKHBRD*AD series in combination with an
EMRQ outdoor unit. Please read this information carefully. It
overrules the standard information foreseen in the installation and
operation manual.
Combination
The unit is the indoor part of the air to water heat pump system. The
unit can only be combined with an ERSQ, ERRQ or EMRQ outdoor
unit.
Connecting to a benefit kWh rate power supply
The EKHBRD*AD indoor unit and ERSQ and ERRQ outdoor unit can
be connected to a benefit kWh rate power supply.
Due to compressor reliability reasons, the EMRQ outdoor unit
cannot be connected to a benefit kWh rate power supply.
Connecting to an EMRQ outdoor unit
For connection and installation of an EKHBRD*AD to an EMRQ
outdoor unit, follow the instructions as described in the installation
manual of the EMRQ outdoor unit. Special attention points are
mentioned below.
Field settings
Field setting [7-00] bottom plate heater cannot be used.
Field piping
Piping between refrigerant branch kit and indoor unit
Pipe size for direct connection to indoor unit must be the same size
as the connection size of the indoor unit.
Capacity index to be allocated to EKHBRD*AD unit
The index as described in the table below, can be used to check the
connection ratios and to select the refrigerant branch kits.
A Addendum to installation manual
EKHBRD*AD
Discharge gas pipe Liquid pipe
Ø15.9 mm Ø9.5 mm
Indoor unit Capacity index
EKHBRD011*AD 100
EKHBRD014*AD 125
EKHBRD016*AD 140