Daikin CHYHBH05AAV32 [10/32] Installation

Daikin CHYHBH05AAV32 [10/32] Installation
4 Installation
Installation manual
10
CHYHBH05+08AA
Daikin Altherma R Hybrid
4P471756-1E – 2019.09
Routing Possible cables (depending on unit type and installed options)
b Interconnection cable between indoor unit and gas boiler (see boiler manual for connection instructions)
c Outdoor ambient temperature sensor (option)
User interface
Indoor ambient temperature sensor (option)
Safety thermostat (field supply)
3 Fix the cable with cable ties to the cable tie mountings to
ensure strain relief and to make sure that it does NOT come in
contact with the piping and sharp edges.
CAUTION
Do NOT push or place redundant cable length in the unit.
NOTICE
More technical specifications of the different connections
are indicated on the inside of the indoor unit.
4.5.2 To connect the main power supply of the
indoor unit
1 Connect the main power supply.
X2M
X1M
1
2
3
X5M
1 2 3
1 2 3
a
a Interconnection cable (=main power supply)
2 Fix the cable with cable ties to the cable tie mountings.
4.5.3 To connect the user interface
If you use 1 user interface, you can install it at the indoor unit (for
control close to the indoor unit), or in the room (when used as
room thermostat).
If you use 2 user interfaces, you can install 1 user interface at the
indoor unit (for control close to the indoor unit) + 1 user interface
in the room (used as room thermostat).
# Action
1 Connect the user interface cable to the indoor unit.
Fix the cable with cable ties to the cable tie mountings.
X1M
1
2
X5M
ab
a Main user interface
(a)
b Optional user interface
2 Insert a screwdriver into the slots underneath the user
interface and carefully separate the faceplate from the
wallplate.
The PCB is mounted in the faceplate of the user interface.
Be careful NOT to damage it.
3 Fix the wallplate of the user interface to the wall.
4 Connect as shown in 4A, 4B, 4C or 4D.
5 Reinstall the faceplate onto the wallplate.
Be careful NOT to pinch the wiring when attaching the
frontplate to the unit.
(a) The main user interface is required for operation, but has to
be ordered separately (mandatory option).
4A From the rear
b
a
PCB
4B From the left
a
PCB
b