Packaged Rooftop
17
We reserve the right to make changes without any prior notice.
UATYA
4P645203-1
5.2 Set point management
The control setpoint mainly depends on parameters “ST1” and “STH1”.
The relevant settable minimum and maximum setpoint parameters are shown below.
Parameter Min Max UM Description
ST1 ST2 ST3 °C Mechanical cooling - Temperature setpoint
STH1 STH2 STH3 °C
Mechanical heating / Auxiliary heating in winter mode - Temperature
setpoint
Provision has been made for ancillary functions that are designed to either add or subtract an o󰀨set value to/from
these setpoints.
Any automatic variation of the setpoint must be within the corresponding limits.
Parameter “SD2” is used to set the operating mode in which setpoint variation is enabled. There is
only one function available and this is the function enabled at the factory.
5.2.1 Dynamic Set Point
The dynamic set point is a function enabled by the manufacturer.
The reference parameters in managing the dynamic set point are described below.
Parameter Min Max UM Description
ST1 ST2 ST3 °C Mechanical cooling - Temperature setpoint
STH1 STH2 STH3 °C
Mechanical heating / Auxiliary heating in winter mode - Temperature
setpoint
SD2 0 2 - States of the unit in which it is active
SD10 0.0 55.0 °C
Mechanical cooling - External air temperature - Activation threshold
for compensation
SD20 0.0 55.0 °C
Mechanical heating - External air temperature - Activation threshold
for compensation