5.3 Temperature control
Cooling and heating devices are controlled according to the temperature value measured by a reference probe.
The proportional band identies the control range of the air conditioner system and it can be set up with independent
values for heating and cooling mode.
The dead zone identies the range around the setpoint within which the devices are not enabled (it is used to prevent
oscillations in the setup value).
The diagram below shows the behaviour of heating and cooling devices.
STH6STH4
100
0
%
STH1
SdR °C
STH5
ST5
ST6
ST4
ST1
Fig. 3 Graphical representation of temperature control devices
Parameter Min Max UM Description
ST1 ST2 ST3 °C Mechanical cooling - Temperature setpoint
ST4 0.0 25.0 °C Proportional control - Cooling - Activation di󰀨erential
ST5 0.0 25.0 °C Proportional control - Cooling - Neutral activation area
ST6 0.0 25.0 °C Proportional control - Cooling - O󰀨set
ST9 0 7 - Control probe
ST11 0 2 - Type of temperature control
PID70 0 10000 - Mechanical cooling - Kp
PID71 0 10000 - Mechanical cooling - Ki
PID72 0 10000 - Mechanical cooling - Kd
PID76 0.0 25.0 °C Mechanical cooling - Dead band
PID78 0 2 - Mechanical cooling - Dead band position
STH1 10.0 35.0 °C
Mechanical heating / Auxiliary heating in winter mode - Temperature
setpoint
STH4 0.0 25.0 °C Mechanical heating - Proportional - Activation di󰀨erential
STH5 0.0 25.0 °C Mechanical heating - Proportional - Activation neutral zone
STH6 0.0 25.0 °C Mechanical heating - Proportional - O󰀨set