4.7 Air system
4.7.1 Internal air fans
Dependingonthecongurations,theremaybeonlysupplyfansoralsoreturnfansintheunits.
The fans are radial fans with reverse blades, with external rotor motor directly coupled to the impeller.
The radial fans are called "EC", with electronically commutated brushless motor. The fan is powered by mains AC
voltage, and speed control is obtained via DC 0-10V control signal coming from the microprocessor installed on the
unit.Thismakesitpossibletosettheairowratethroughtheparameterbeingdisplayed.
The motors have alarm signalling, which includes thermal overload protection, overcurrent, undervoltage, absence
ofoneormorephasesandseizedrotor.
The EC fans are not provided with a contactor and are constantly live as soon as the main disconnect
switch of the unit is closed.
4.7.2 Flow rate sensor for fans
Unitswith"EC"fansareprovidedwithadi󰀨erentialpressuretransducerthatdetectsthepressuredi󰀨erencebetween
theinsideandtheoutside(upstream)oftheintakenozzle.Theairowrateisproportional,foreachfan/nozzlepair,
tothesquarerootofthepressuredi󰀨erenceaccordingtotheequation:
where
- Q=totalairow[m3/h]
- n = number of fans in the unit
- k=constantaccordingtothefannozzle
- ΔP=pressuredi󰀨erencemeasuredonthenozzle[Pa]
Thecharacteristicconstant"K"forthenozzlesusedis:
- Fan of diameter 450: k = 217
- Fan of diameter 500: k = 281
- Fan of diameter 560: k = 350
Thedi󰀨erentialpressurevalueandtheairowratecanbeshowndirectlyonthedisplayofthemicroprocessorthat
carriesoutautomaticcontroloftheairowrate.
4.7.3 Airowsensor
Thisdevicepreventstheunitoperatingintheabsenceofairow.Thecontroliscarriedoutbyadi󰀨erentialpressure
switchthatmeasuresthepressuredi󰀨erencebetweenupstreamanddownstreamoftheevaporatingcoilandtheair
lter.Themicroprocessoralarmcomesonlaterthaninterventionofthesensor.
To check their operation, open the automatic circuit breakers of the compressors, from the microprocessor card
removetheterminalwiththecontrolsignalfortheECfan(foridentication,refertothewiringdiagram),andthen
switch on the unit. The microprocessor alarm should appear within a few tens of seconds.