6.4 Checks during operation
Withthecircuitsoperatingat100%andstableatworkingconditionsnearthenominalones,check:
- thattheelectricalabsorptionoftheunitisclosetothedatashowninthewiringdiagram.Considerablydi󰀨erent
valuesmaybeduetothereducedcapacityoperationoftheunit,toworkingconditionsverydi󰀨erentfromthe
nominal ones or to the malfunctioning of one or more components.
- thatthedi󰀨erencebetweenthecondensingtemperatureofeachcircuitandthatoftheairislessthan25°C.Ifit
is greater, check that all the fans involved are turning correctly and that there are no obstructions or dirt on the
surface of the condensing coil;
- thesuperheatingvalueofthesuctiongas:theoptimalvalueisbetween4and7°C;
- thesubcoolingvalueoftheliquidleavingthecondenser:theoptimalvalueisbetween5and10°C;
- thattheliquidsightglassisgreen;
- thatnobubblesappearonthesightglassplacedintheliquidpipe.Thecontinuouspresenceofbubblesmay
indicate a lack of refrigerant charge; the occasional or sporadic presence of bubbles is allowed;
- thattherefrigerantlterisnotblockedorclogged.Tothisend,itissu󰀩cienttomeasurethetemperatureofthe
liquidpipeimmediatelybeforeandimmediatelyafterthelter,andcheckthattherearenosignicantdi󰀨erences
(uptoacoupleofdegreesCdi󰀨erenceisallowed).
- that the condensate drain is working correctly.