5. Service Diagnosis
On completion of installation (P.4 3. Connection Drawing), turn the outdoor unit power ON and make sure that
pressures are displayed normally.
Abnormal display: Refer to “Service Diagnosis” below and take necessary remedies if no figures are
displayed. If the trouble do not fall under any of the items described, change the Digital Pressure Gauge Kit.
Error display and measurements
Error display Cause Remedy
1
The LED indicator is not lit
Power supply is not provided
to the outdoor unit.
Provide power supply to the outdoor unit.
The connector of the power
supply line is unplugged.
Insert the connector of the power supply
line.
The power supply line is
disconnected or damaged.
Replace the power supply line.
Others
Please change the Digital Pressure
Gauge Kit.
2
All LEDs blink
The connector of the
communications line is
unplugged.
Plug in the connector of the
communications line.
The communications line is
disconnected or damaged.
Replace the communications line.
The outdoor unit is not
compatible with the Digital
Pressure Gauge Kit.
Check with a this service manual if the
outdoor unit is compatible with the Digital
Pressure Gauge Kit.
If the outdoor unit is not compatible, this
Digital Pressure Gauge Kit cannot be
used.
Others
Please change the Digital Pressure
Gauge Kit.
3
There is a high-voltage line
generating noise around the
communications line.
Noise may be imposed on the
communications line. Separate the high-
voltage line.
The outdoor unit has a defect.
Refer to the Service Guide and remedy
the problem.
Others
Please change the Digital Pressure
Gauge Kit.
blinks