Daikin LRMEQ6AY1E [6/17] Connection drawing
![Daikin LRMEQ8AY1 [6/17] Connection drawing](/views2/1801930/page6/bg6.png)
5
Connection drawing
1. Turn the outdoor unit power OFF.
2. Remove the front panel. (If the model has two front panels (i.e., one each on the left-hand side and right-
hand side), remove the panel on the right-hand side only.)
3. Remove the lid of the electrical box.
4. Refer to the and mount the Digital Pressure Gauge Assembly to the panel on the right-
hand side.
[Parts used: Digital Pressure Gauge Assembly: 1, M5×12 screw: 2]
5. Secure the ground wire to the electrical box with a screw.
Refer to section B (detail view) in the for the screwing position.
[Parts used: M4×12 screw: 1]
6. Connect the power supply line and communication line of the Digital Pressure Gauge
Assembly to the control PCB (A1P) in the electrical box.
• Power supply line: Connector (white) • X77A
• Communication line: Connector (blue) • X27A
At that time, wire the communication line behind the Digital Pressure Gauge Assembly.
(Refer to section A (detail view) in the .)
7. After connecting the power supply line, communication line, and ground wire, secure the wiring path
according to the .
[Parts used: Clamps: small 6, large 1]
8. Mount the lid of the electrical box.
9. Punch out the knock hole with a diameter of 70 mm on the front panel. (Refer to the mounting dimensions
on the upper right-hand side.)
10.Attach the resin bush to the knock hole on the front panel. [Parts used: Resin bush: 1]
11.Mount the front panel.
12.On completion of installation, turn the outdoor unit power ON and make sure that pressures are displayed
normally.
When figures appear in the discharge pressure display and suction pressure indicate, the product is
working normally.
(Pressure is indicated in the operation switch "OFF or ON" of outdoor unit.)
Abnormal upper section: Error code, Abnormal lower section: LP
Abnormal display case: Please refer to the service diagnosis P.15
C: 2P190979
Knock hole on the front panel
Punch out the
knock hole on the
left-hand side.
Installation drawing
Wiring drawing
Wiring drawing
Wiring drawing
Содержание
- Bhgp26a1 e h 1
- Connected model 1
- Digital pressure gauge kit 1
- Failure diagnosis tool for zeas_a type 1
- Contents 2
- Table of contents 2
- Check the software of condensing unit 3
- Communicated image 3
- Condensing unit 3
- Digital pressure gauge kit 3
- Overview of product 3
- Preparation before connection of digital pressure gauge kit 3
- Specification of digital pressure gauge kit 4
- Connection drawing 5
- Discharge 5
- Label pasting drawing 5
- Mm max 5
- Section a 5
- Section a detail view 5
- Section b 5
- Section b detail view 5
- Suction 5
- Wiring drawing 5
- Connection drawing 6
- Knock hole on the front panel 6
- Attention in the display 7
- Digital pressure gauge kit and ram monitor can not be used at the same time for communication line is connected to x27a of control pcb of outdoor unit 7
- Installation drawing 7
- Abnormal 8
- Display item 8
- Display item and method of operation 8
- Normal 8
- Cautions for manual operation display 1 9
- Manual operation display 1 9
- 1 for a display example te0 is displayed refer to the detailed information of display items on the following page onward 10
- H h k h h h h 10
- H k k h h h h 10
- L h h l h h h 10
- L h k h h h k 10
- L h k h h h l 10
- L h l h h h h 10
- Table1 operation method of manual operation display 1 10
- 1 no display is available as target equipments are not present 2 in case each sensor is abnormal correct value can not be displayed before checking the sensor measurement please check if there is an abnormal report 11
- Table2 display items of manual operation display 1 11
- 1 no display is available as target equipments are not present 2 in case each sensor is abnormal correct value can not be displayed before checking the sensor measurement please check if there is an abnormal report 12
- Cautions for manual operation display 2 14
- Display example 14
- Each display item is displayed by automatic scroll interval of 3 sec in the order of display no 2 after display no 3 displayed automatically returns to display no 1 3 after 120 minutes of automatic scroll the display is automatically returned to the initial display so that it will not be lost 4 if booster unit is abnormal a batch of error codes from outdoor units such as 14
- Etc are displayed 14
- In case no error is present 14
- Manual operation display 2 14
- On the manual operation display 2 you can check error history for the preceding 3 times in this case both upper and lower sections show lighting display the upper section indicates how many times error occurred in the history the lower section displays error code 14
- Table 3 on p 14 shows how to set manual operation display 2 14
- H h k h h h h 15
- H k k h h h h 15
- L h h l h h h 15
- L h k k h h h 15
- L h l l h h h 15
- Table3 operation procedure of manual operation display 2 15
- Error display and measurements 16
- On completion of installation p 3 connection drawing turn the outdoor unit power on and make sure that pressures are displayed normally abnormal display refer to service diagnosis below and take necessary remedies if no figures are displayed if the trouble do not fall under any of the items described change the digital pressure gauge kit 16
- Service diagnosis 16
- Led of outdoor unit flow 17
- Segment flow manual operation display 1 17
- Segment flow manual operation display 2 17
- The entire flow 17
Похожие устройства
- Daikin LRMEQ6AY1E Инструкция по эксплуатации
- Daikin LRMEQ6AY1E Сервис мануал
- Daikin LRMEQ6AY1E Инструкция по монтажу
- Daikin LRMEQ8AY1 Справочное руководство для монтажника
- Daikin LRMEQ8AY1 Инструкция по эксплуатации
- Daikin LRMEQ8AY1 Сервис мануал
- Daikin LRMEQ8AY1 Инструкция по монтажу
- ZPStrong RFCD-3700 Руководство пользователя
- Interpump IPG WS102 Инструкция по эксплуатации
- Interpump IPG WS102 Брошюра
- Interpump IPG WS102 Схема запасных частей
- Interpump IPG W1550 (1450 об/мин) Инструкция по эксплуатации
- Interpump IPG W1550 (1450 об/мин) Брошюра
- Interpump IPG W1550 (1450 об/мин) Схема запасных частей
- Interpump IPG W5015 (1450 об/мин) Инструкция по эксплуатации
- Interpump IPG W5015 (1450 об/мин) Брошюра
- Interpump IPG W5015 (1450 об/мин) Схема запасных частей
- Interpump IPG W 5015 (1450 об/мин) Инструкция по эксплуатации
- Interpump IPG W 5015 (1450 об/мин) Брошюра
- Interpump IPG W 5015 (1450 об/мин) Схема запасных частей