Haier AC242ACERA [368/408] Troubleshooting

Haier AB182ACERA [368/408] Troubleshooting
replace module
adjust wiring
no
if problem is solved
yes
replace PCB
no
check if the wiring between
outdoor PCB and module is
correct
no
Outdoor indicator shows 11000.
Alarm condition: outdoor system pressure is lower than 0.05MPa.
12) Outdoor low pressure abnormal
outdoor indicator shows 11000
yes
no
low pressure
abnormal
replace pressure
switch
yes
dredge piping
check if piping is blocked
yes
check if high
pressure is low,too
Lack of refrigerant, charge
additional refrigerant and check if
piping leaks, if yes, replace piping
measure actual pressure by a
pressure gauge to adjust the
output failure
Troubleshooting
-351-