Loading and Unloading/Transporting Management/Storage Requirements
1) The products shall be carefully handled during loading and unloading.
2) Do not give impact to the indoor and outdoor units, or otherwise product damage may result.
3) Be sure to read the safety cautions before conducting any work.
4) Dry powder extinguishers or other suitable fire extinguishing apparatus should be equipped at the loading area.
5) Untrained personnel cannot be engaged in loading and unloading of air conditioners with flammable refrigerants.
6)
Smoking and open fire are not allowed around the air conditioner.
Transporting Management Requirements
1) The maximum transporting volume of finished products shall be determined as per local regulations.
2) The vehicles used for transporting shall be operated as per local laws and regulations.
3) Dedicated after-sales vehicles shall be used for maintenance transportation, and exposed transporting of
refrigerant cylinders and the products to be maintained is not allowed.
4) A rain cover or similar shield material of the transporting vehicles should have certain flame retardancy.
5) Leakage warning device of flammable refrigerant shall be installed inside the closed-type compartment.
6) Anti-static device shall be equipped inside the compartment of transporting vehicles.
7) Dry powder extinguishers or other suitable fire extinguishing apparatus shall be equipped inside the driver's cab.
8)
9)
The transporting vehicles shall run at a constant speed, and heavy acceleration/deceleration shall be avoided.
High-temperature area shall be avoided during transporting, and necessary radiating measures shall be taken
in case the temperature inside the compartment is too high.
Storage Requirements
1) The storage package of equipment used shall be such that no leakage of refrigerant will be caused due to
mechanical damage of the equipment inside.
2) The maximum quantity of the equipment allowed to be stored together shall be determined as per local
regulations.
Installation Instructions
WARNING!
The area of the room in which R32 refrigerant air conditioner is installed cannot be less than the minimum
area specified in the table below, to avoid potential safety problems due to out-of-limit of refrigerant
concentration inside the room caused by leakage of refrigerant from refrigeration system of the indoor unit.
Once the horn mouth of connecting lines is fastened, it may not be used again (the air tightness may be
affected).
A whole connector wire shall be used for indoor/outdoor unit as required in the operation specification of
installation process and operation instructions.
Minimum Room Area
Type
LFL
kg/m3
hv
Total Mass Charged/kg
Minimum Room Area/m
2
R32 0.306
4 7 10 15 20
0.6
9
1
1.0
1
1
1.8
2.2
m
3
The maximum refrigerant charge amount (M)
Indoor unit Outdoor unit M kg
AS26DCBHRA 1U26JABFRA
1.3
AS35DCBHRA 1U35JABFRA
1.4
AS53DDBHRA 1U53RAAFRA
1.7
Содержание
- Room air conditioner installation manual 1
- Contents 2
- Keep this manual where the user can easily find it 3
- Read the precautions in this manual carefully before operating the unit this appliance is filled with r32 3
- Warning 3
- Cautio 4
- How to use dred appliance 4
- Important information rega rding the refrigerant used 4
- The maximum refrigerant charge amount m 5
- Maintenance items 11
- Adhesive tape 14
- Air inlet 14
- Air outlet 14
- Compressor inside of unit 14
- Drain hose 14
- Heating insulating material 14
- Indoor outdoor unit installation drawings 14
- Non adhesive tape 14
- Optional parts for piping 14
- Piping hole cover 14
- Please be subjected to the actual product purchased 14
- Saddle l s with screws connecting electric cable for indoor and outdoor drain hose 14
- The marks from to in the gure are the parts numbers the indoor unit should be installed at the recommended height 2m 14
- When installing the unit to wall roof or rooftop fix a supporter surely with nails or wires in preparation of earthquake and strong wind 2 air conditioner mounted not above and one meter away from electric equipment such as television 14
- Hfc 410a 21
- Cushion rubber 22
- Installation dimension unit mm 22
- Caution 23
- Connection of pipes 23
- Ceramic type of ac 250v t25a 26
- U53raafra 26
- Outdoor unit 27
- Australia 1300 729 948 haier com au new zealand 0800 424 372 haier co nz 28
- For haier appliances 28
Похожие устройства
- Haier 1U35JABFRA Инструкция по монтажу
- Haier 1U53RAAFRA Инструкция по монтажу
- Haier ABH090K5ERG Руководство по монтажу
- Haier ABH090K5ERG Инструкция по эксплуатации
- Haier ABH090K5ERG Инструкция по монтажу
- Haier ABH090K5ERG Брошюра
- Haier ABH105K5ERG Руководство по монтажу
- Haier ABH105K5ERG Инструкция по эксплуатации
- Haier ABH105K5ERG Инструкция по монтажу
- Haier ABH105K5ERG Брошюра
- Haier ABH125K5ERG Руководство по монтажу
- Haier ABH125K5ERG Инструкция по эксплуатации
- Haier ABH125K5ERG Инструкция по монтажу
- Haier ABH125K5ERG Брошюра
- Haier ABH140K5ERG Руководство по монтажу
- Haier ABH140K5ERG Инструкция по эксплуатации
- Haier ABH140K5ERG Инструкция по монтажу
- Haier ABH140K5ERG Брошюра
- Haier ABH071H5ERG Инструкция по монтажу
- Haier ABH071H5ERG Руководство по монтажу