Haier AU282FHERA Руководство по эксплуатации онлайн [5/69] 617242

Haier AU482FIERA Руководство по эксплуатации онлайн [5/69] 617244
3
Model AU282FHERA AU482FIERA (G)
Outdoor coil
Number of rows 2 2
Tube pitch (a)
×
row pitch (b) mm 19.05×22 19.05×22
Fin spacing mm 1.70 1.5
Fin type (code)
HYDROPHILIC
ALUMINIUM
HYDROPHILIC
ALUMINIUM
Fin coating type Optional Clear lacquer Clear lacquer
Salt spray test duration Hour 168 168
Tube outside dia. and type
INNERGROOVE TUBE INNERGROOVE TUBE
mm Ф8 Ф8
Coil length
×
height mm 955×792 970×1200
Number of circuits 4 6
Cabinet coating
Coating type Powder coating Powder coating
Salt spray test duration Hour 72 72
Sheet metal material Hot zinc plate Hot zinc plate
Sheet metal thickness mm 0.8 0.8
Control panel enclosure IP class Standard IP24 IP24
Outdoor air ow m
3
/h 3500 6500
Outdoor sound level (sound pressure level ) dB (A) 55 59
Outdoor sound level (sound power level ) dB (A) 66 70
Outdoor unit
Dimension (W*H*D) mm 960×380×830 960×380×1250
Packing (W*H*D) mm 1095×410×985 1095×410×1400
Net weight kg 74 105
Gross weight kg 89 113
Refrigerant
Type R410A R410A
Charged volume kg 2.6 3.6
Throttle type EXV EXV
Design pressure MPa 4.15 4.15
Refrigerant piping
Liquid pipe mm 9.52 9.52
Gas pipe mm 15.88 19.05
Total pipe length m 50 100
Max. pipe length
(Equivalent/ Actual)
m 35 70
Max. Diff. indoor/outdoor unit m
30 (Outdoor higher than indoor)
20 (Indoor higher than outdoor)
Max. Diff. indoor/indoor unit m 10 10
Connectable indoor unit ratio % 50%~130% 50%~130%
Maximum indoor units Piece 4 8
Connection wiring
Power wiring mm
2
6 10
Signal wiring mm
2
Shield wire: (0.75-2)*2 Shield wire: (0.75-2)*2
Operation range °C
Cooling: 10~43
Heating: -15~21
Cooling: -15~43
Heating: -15~21
Nominal condition:
Indoor temperature (cooling): 27 DB(°C)/19 WB(°C), indoor temperature (heating): 20 DB(°C)/14.5 WB(°C).
Outdoor temperature (cooling): 35 DB(°C)/24 WB(°C), outdoor temperature (heating): 7 DB(°C)/6 WB(°C).
The data is measured with 7.5m equivalent pipe and 0m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a real
time analyser calibrated sound intensity meter. It is a sound pressure noise level.