Haier AB142FCBIA [74/126] Commercial air conditione

Haier AB092FCBIA [74/126] Commercial air conditione
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
In cooling mode, frequency will be calculated according to
the horse power of the running indoor units:
1. Every indoor unit will confirm 8 capacity codes
according to the difference between the set temperature
and the ambient temperature; then add all the capacity
code of the running indoor unit.
2. Divide the outdoor capacity into 13 capacity classes due
to the frequency; every capacity class is corresponding
with the different indoor capacity code; modify the relative
indoor capacity code due to the different ambient
temperature;
3. Compressor will confirm its target frequency according
to the sum of indoor capacity code;
Cooling target frequency
will be confirmed due to the
indoor running horse power
and the outdoor ambient
temperature:
F=C1(P-C2)+C3(T-35)+C4
Herein: C1=22, C2=160,
C3=64, C4=4200;
9
Compress
or capacity
output
control
Heating target frequency will be confirmed due to the indoor running horse power and the
outdoor ambient temperature:
F=C1(P-C2)+C3(7-T)+C4+C5(C6-TZ)
Herein: C1=16; C2=160; C3=32; C4=4500; C5=300; C6=45.
-74-

Содержание

Скачать