Haier AB142FCBIA [89/126] Commercial air conditione

Haier AB092FCBIA [89/126] Commercial air conditione
11
Outdoor fan mode :_1˄low speed˅,_2˄med speed˅,_3˄high speed˅
12
Temperature sensor ON display ON˖
1ˈOFF˖--
13
Four-way valve switched on: ON˖
1 Four-way valve not switched on: OFF˖_ _
14
Running mode selection cooling˖
C, heating: H
0
1
Dispatch line check cooling
˖
CC --this function is preset
2
Dispatch line check heating
˖
HH--this function is preset
3
Cool trial run
˖
C --this function is preset
4 Heat trial run: H --this function is preset
5 Swing trial run: _F--this function is preset
6
Indoor unit uniform start/stop
˖
run: 11/stop: 00
˄
display -- after 3 minutes
˅
--this function is preset
7 Clean abnormal function: CL--this function is preset
8
Outdoor PMV1fully openǃclose function: fully open: FF, fully close: 00
9
Outdoor PMV2 fully openǃclose function: fully open: FF, fully close: 00
10
Indoor PMV fully openǃclose function˖fully open: FF
2
11 Outdoor rated setting: -F
0—7
Indoor communication state: receiving normal˖
1 receiving abnormal:
3
8 Display quantity of communicating indoor unit, e.g. : 6 shows that 6 indoor units
are working.
4 0—15 Indoor diagnosis code, no diagnosis code: --this function is preset
5 0—15 Indoor HP
new code:0 stands for 0.8HP, 1 stands for 1HP, 2 stands for 1.2HP,
3 stands for 1.5HP, 4 stands for 2HP, 5 stands for 2.5HP, 6 stands for 3HP, 7
stands for 4HP
Old code: 1 stands for 1HP,7 stands for 7HP
6 0—15 Indoor required capacity (decimalism) indoor P-CODE
7 0—15 Indoor PMV opening degree (decimalism)
8 0—15
Indoor saturation temperature (decimalism) -26.0—67.0˄account according to
outdoor suction pressure PS˅
9 1—16
Indoor sensor TA temperature˄decimalism˅-26.0—67.0
10 1—16
Indoor sensor TC2 temperature˄indoor gas pipe˅˄decimalism˅-26.0—100.0
11 1—16
Indoor sensor TC1 temperature˄indoor liquid pipe˅˄decimalism˅-26.0—100.0
12 1—16 Single cool trial run--this function is preset
13 1—16 Single heat trial run--this function is preset
Combination control with outdoor switches
Table 2
function summary Method of set, cancel
Cool trial run Indoor trial run in cooling
mode, the function is the
same as trial run with remote
controller, the indoor unit
which trials run fixes the temp.
difference as max. temp., and
send it to outdoor, the other
control is similar with normal.
[set]
SW01“2”, SW02“03”, press SW04 for more
than 2 seconds, after set of trial run success, LD
will always display –C until the function is
cancelled.
[cancel]
in trial run state, SW01“02”, SW02“03”, press
SW05
Heat trial run Indoor trial run in heating
mode, the function is the
same as trial run with remote
controller, the indoor unit
which trials run fixes the temp.
difference as max.
[set]
SW01“2”, SW02“04”, press SW04 for more than
4 seconds, after set of trial run success, LD will
always display –H until the function is cancelled.
[cancel]
in trial run state, SW01“02”, SW02“03”,
p
ress
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
-89-