Haier AB142ACBIA [71/365] Shows resumable fault shows it is not resumable fault setting address method the address setting can be realized by setting indoor pcb if you use the group control function there should be a master unit and 15 sets of slave units for the master unit the sw5 3 should be at on for the slave units the sw5 3 should be at off please refer the below table indoor unit address sw1 4 sw1 3 sw1 2 sw1 1

Haier AU282AHBEA [71/365] Shows resumable fault shows it is not resumable fault setting address method the address setting can be realized by setting indoor pcb if you use the group control function there should be a master unit and 15 sets of slave units for the master unit the sw5 3 should be at on for the slave units the sw5 3 should be at off please refer the below table indoor unit address sw1 4 sw1 3 sw1 2 sw1 1
>a__WcU[S^ <[c >a`V[e[a`Wc
-71-
sensor abnormal short circuit for more than
2m continuously
13 0D 31D Solenoid valve
abnormal
Solenoid valve act
incorrectly 3 times
continuously
14 4C 15D Discharging temp.
sensor abnormal
Sensor broken down or
short circuit for more than
2m continuously
15 05 17D EEPROM abnormal EEPROM data missing Run as the
default
value
16 54 26D Pressure
abnormal(low
pressure)
Low pressure switch acts in
normal running
17 50 15D Compressor overheat the discharging
temperature is higher than
120degree
Resumable
if lower
than
100degree
18 0C 23D Abnormal mode Indoor operation mode is
different with the running
indoor unit.
19 4B 18D Outdoor coil
B(suction temp
sensor—for MRV II)
Sensor broken down or
short circuit for more than
2m continuously
20 4D 15D Outdoor discharging
B(oil temp
sensor—for MRV II)
Sensor broken down or
short circuit for more than
2m continuously
21 32 07D Power module failure Power module overheat, or
over current, or short circuit
22 54 08D No load Sensor abnormal or the
compressor not start up
shows resumable fault, shows it is not resumable fault.
Setting address method:
The address setting can be realized by setting indoor PCB.
If you use the group control function, there should be a master unit and 15 sets of slave units.
For the master unit, the SW5-3 should be at “ON”. For the slave units, the SW5-3 should be
at “OFF”.
Please refer the below table,
Indoor
unit
address
SW1-4 SW1-3 SW1-2 SW1-1
1 OFF OFF OFF OFF
2 OFF OFF OFF ON