Haier AC092FEBHA [10/12] Operation control
![Haier AC162FEAHA [10/12] Operation control](/views2/1822091/page10/bga.png)
9
CN02 CN12 CN01
indoor control borard
A
B
C
A
B
C
A
B C
remote
controller
group control
indoor unit
(#1) (#2-16)
indoor unit indoor unit
Solution of group control
One set of remote controller can control a group of 16 indoor unit at the most.
Refer to electrical wiring layout items for wiring layout between indoor unit.
Arrange wires between remote controller and indoor unit according to the following sequence:
(1)Set number setting switch SW01 on PC board of each indoor unit with number 1 as ì1î,
number 2 as ì2î ÖÖ (the machine directly connecting remote controller must be set as number
1î). Number 1 is the host while others are subsidiaries.
(2)Connect terminals A, B, C of the remote controller with that of number 1 indoor unit respectively
(according to same numbers).
(3)Connect terminals B, C of number 1 indoor unit with that of number 2 respectively
(according to same numbers).
(4)Connect terminals B, C of number 2 indoor unit with that of number 3 respectively
(according to same numbers).
(5)By analogy of the above, stop until connecting to terminals B, C of number 16 (at the maximum).
(6)Disassemble short connection wire to CN12 terminal on control base board of number 2-16 indoor
subassemblies to prevent wrong connection that may cause defects.
Requirement
Wires of remote controller between indoor unit should be power
cord more than 1mm≤ with length less than 500 m (total length from
remote controller to number 16 machine).
Setting of group number of indoor subassemblies
Code switch AW02 on base board of indoor unit has
the function of setting centralized control address (group number).
Group number can be set by changing ìON/OFFî status in ì1-6î code positions.
Code switch SW02 and its dialing codes are shown as following diagram:
Relation between combination of
ìON/OFFî status in ì1-6î
code positions and group
number are shown as in right table.
When ì7î position of SW02 is in ìOFFî
status, group number can be set either by
dialing codes on SW02 or with circuit
controller. While ì7î position of SW02
is in ìONî status, group number can only
be set either by dialing codes on SW02.
ON
OFF
1 2 3 4 5 6 7
ON
Wiring layout of centralized controller should be done according to installaiton manual of centralized controller
Operation control
Selection of
group number
01
x x x x x x
02
x x x x x
03
x x x x
x
04
x x x x
05
x x x
x
x
06
x x x
x
07
x x
x
x
08
x x x
09
x x
xx x
10
x x
x
x
11
x x
x
x
12
x x
x
13
x x
x
x
14
x x
x
15
x x
x
16
x x
:ON
x:OFF
Status shown in the above is
number 16 in a control group
For example:
ON
1 2 3 4 5 6 7
380-400V,3N~,50Hz
outdoor power
junction box
indoor unit
1PH,220-230V~,50Hz
earth
communication wire
shield layer earth
shield layer should be
connected together
(
shield layer as isolation
)
leak breaker manual switch
remote controller
grouped control
(
shield layer as isolation
)
(
shield layer as isolation
)
(
shield layer as isolation
)
indoor unit
shield layer should be
connected together
centralized control signal wire earth
centralized control signal wire
(centralized controller)
communication wire
leak breaker manual switch
indoor power
1PH,220-230V~,50Hz
remote
controller
Содержание
- Safety precautions 2
- Notice 3
- Selection of installation place 3
- Installation in under ceiling 4
- Installation of air conditioner 4
- Installation of suspending bolts 4
- Prior to installation 4
- Directly use angle iron to set supporting angle iron use inlet hinge joint inlet plug or inlet bolt 5
- Fasten hexagon bolt and fix the air conditioner 5
- Insert hexagon bolt into carved fillet 5
- Install beam wood on the girder and set suspending bolts 5
- Installation of air conditioner 5
- Installation of air conditionert 5
- Installation of attached hexagon bolt 5
- Installation position of suspending bolts 5
- Installation status of supporting frame 5
- Internal suspension ac092 122 142 162feaha ac092 122 142 162febha 5
- Internal suspension ac182 242 282feaha ac182 242 282febha 5
- Please refer to positions of suspending bolts printed on installation paste board of ac092 122 142 162feaha ac092 122 142 162febha type 5
- Steel structure old concrete building 5
- Wood building new concrete building 5
- Installation of floor console 6
- Refrigerant distribution tube 7
- Requirentents 8
- Undulation 8
- Electric wiring 9
- Remote controller wire 9
- Code switch aw02 on base board of indoor unit has the function of setting centralized control address group number group number can be set by changing ì on offî status in ì 1 6î code positions code switch sw02 and its dialing codes are shown as following diagram 10
- One set of remote controller can control a group of 16 indoor unit at the most refer to electrical wiring layout items for wiring layout between indoor unit arrange wires between remote controller and indoor unit according to the following sequence 1 set number setting switch sw01 on pc board of each indoor unit with number 1 as ì 1î number 2 as ì 2î ö ö the machine directly connecting remote controller must be set as number 1î number 1 is the host while others are subsidiaries 2 connect terminals a b c of the remote controller with that of number 1 indoor unit respectively according to same numbers 3 connect terminals b c of number 1 indoor unit with that of number 2 respectively according to same numbers 4 connect terminals b c of number 2 indoor unit with that of number 3 respectively according to same numbers 5 by analogy of the above stop until connecting to terminals b c of number 16 at the maximum 6 disassemble short connection wire to cn12 terminal on control base board of numb 10
- Operation control 10
- Relation between combination of ì on offî status in ì 1 6î code positions and group number are shown as in right table when ì 7î position of sw02 is in ì offî status group number can be set either by dialing codes on sw02 or with circuit controller while ì 7î position of sw02 is in ì onî status group number can only be set either by dialing codes on sw02 10
- Requirement 10
- Setting of group number of indoor subassemblies 10
- Solution of group control 10
- Wires of remote controller between indoor unit should be power cord more than 1mm with length less than 500 m total length from remote controller to number 16 machine 10
- Settings of heating temperature compensation usage of switch sw03 11
- Usage of emergency switch usage of switch sw04 11
- Disorders in trial run 12
- Notice 12
- Requirement 12
- Trial run 12
Похожие устройства
- Haier AC092FEBHA Инструкция по эксплуатации
- Haier AC122FEAHA Инструкция по монтажу
- Haier AC122FEAHA Инструкция по эксплуатации
- Haier AC122FEBHA Инструкция по монтажу
- Haier AC122FEBHA Инструкция по эксплуатации
- Haier AC162FEAHA Инструкция по монтажу
- Haier AC162FEAHA Инструкция по эксплуатации
- Haier AC162FEBHA Инструкция по монтажу
- Haier AC162FEBHA Инструкция по эксплуатации
- Haier AC182FEAHA Инструкция по монтажу
- Haier AC182FEAHA Инструкция по эксплуатации
- Haier AC182FEBHA Инструкция по монтажу
- Haier AC182FEBHA Инструкция по эксплуатации
- Haier AC242FEAHA Инструкция по монтажу
- Haier AC242FEAHA Инструкция по эксплуатации
- Haier AC242FEBHA Инструкция по монтажу
- Haier AC242FEBHA Инструкция по эксплуатации
- Haier AC282FEAHA Инструкция по монтажу
- Haier AC282FEAHA Инструкция по эксплуатации
- Haier AC282FEBHA Инструкция по монтажу