Detach the charge hose from the service port, open
3-way valve and 3-way. Turn the valve rod
anticlockwise until hitting lightly.
6
In case of gas leakage, tighten
parts of pipe connection. If
leakage stops, then proceed
steps.
No gas leakage?
5
4
Open the valve rod for the 3-way valve to and angle of
anticlockwise 90 degree.
After 6 seconds later, close the 3-way valve and male
the inspection of gas leakage.
Vacuumize for over 15min. And check the level gauge
which should read -0.1 MPa (-76 cm Hg) at low
pressure side. After the completion of vacuumizing,
close the handle 'Lo' in gaugemanifold and stop the
operation of the vacuum pump.
Check the condition of the scale and hold it for 1-2min.
If the scale-moves back in spite of tightening, make
flaring work again, the return to the beginning of 3 .
Open the handle at low in gaugemanifold, operate
vacuum pump. If the scale-moves of gause (low)
reach vacuum condition in a moment, check 1 again.
1
Detach the service port's cap of 3-way valve, the
valve rod's cap for 3-way valve and 3-way's, connect
the service port into the projection of charge hose
(low) for gauge manifold. Then connect the projection
of charge hose (center) for gaugemanifold into
vacuum pump.
To use vacuum pump
CAUTION:
If the refrigerant of the air conditioner leaks, it is necessary to make
all the refrigerant out, then charge the liquid refrigerant into air
conditioner according to the amount marked on the nameplate.
2
Open
(4) Purging method ( the refrigerant is R407C)
6
3
Close
8
After attaching the each caps, check the gas leakage
around the caps.
To prevent the gas leakage, turn the service port's
cap, the valve rod'd cap for 3-way valve and 3-way's
a lottle more than the point where the torque increases
suddenly.
7
If it does not stop gas leakage, discharge
whole refrigerants from the serice port.
After flaring work again and vacuumize,
fill up prescribed refrigerant from the gas
cylinder.
1
2
3
ATTENTION:
After finishing installation, please confirm no refrigerant leakage.
051220**
Installation Procedures
Liquid pipe
Gas pipe
Gaugemanifold (R407C)
Vacuum pump
(R407C)
3-way valve
3-way valve
7
7
Valve rod cap
Service port cap
7
3-way valve
3-way valve
Valve rod cap
6
6
3-way valve
3-way valve
90
for
6
sec.
4
Service port
90
90
3-way valve
3-way valve
Содержание
- Cassette type air conditioner 1
- Operation installation manual 1
- Cassette type air conditioner 2
- Contents 2
- Cautions 3
- Disposal of the old air conditioner 3
- Disposal of the packaging of your new air conditioner 3
- Cautions 4
- Specifications 4
- Diferent fan speed 5
- Main points of operation 5
- Minute protection function 5
- Operation of air conditioner 5
- Remote control 5
- Anti cold blowing off 6
- Auto restant function to be applied for a necessary situation 6
- Defrosting function 6
- In heating mode the indoor fan will not run immediately after the unit starts up which will the cold air being blow out 6
- In heating mode when frost is formed on the outdoor heat exchanger the air conditioner will automatically defrost for few minutes during defrosting both indoor fan and outdoor fan will stop running when defrosting finishes air condi tioner will automatically be back to running 6
- Main points of operation 6
- The air conditioner absorbs heat form outdoor and releases to indoor when in heating mode therefore the outdoor environmental temperature will affect heating efficiency 6
- Air filter 7
- Air inlet grille 7
- Indoor unit 7
- Operating control panel 7
- Outdoor unit 7
- Part name 7
- Remote receiver compressor lamp timer lamp operation lamp power lamp emergency switch 7
- Swing louver 7
- Be sure to conform with the following important safety precautions the safety precautions should be at hand so that they can be checked at any time when necessary if the air conditoner is transferred to the new user this manual should be as well transferred to the new user 8
- Below are listed four kinds of safety precautions and suggestions 8
- Carefully read the following information in order to operate the air conditioner correctly 8
- Caution 8
- Incorrect operations may result in injures or machine damages in some cases may cause serious consequences 8
- Incorrect operations may result in severe consequences of death or serious injures 8
- Instruction 8
- It must be strictly prohibited where being marked with ì prohibited î otherwise may result in machine damages or endanger the usersípersonal safety 8
- Safety precautions 8
- This information can ensure the correct operation of the machine 8
- Warning 8
- Safety precautions 9
- Warning 9
- Caution 10
- Clean indoor outdoor unit 10
- Clean the air filter 10
- Clean the unit 10
- Maintenance 10
- Take down air inlet grille 10
- Take down the filter 10
- Maintenance 11
- Post season care 11
- Pre season care 11
- Seasonal reserve 11
- Cold air blown out when heating 12
- Insufficient cooling 12
- Insufficient cooling or heating 12
- When trouble happens 12
- Customer need to know 13
- Using directions 13
- Installation tools 14
- Installation preparation 15
- Installation procedures 15
- Selection of installation place 15
- After installation on the ceiling 16
- In case of no ceiling 16
- In the case of existing ceiling 16
- Installation of indoor unit 16
- Installation procedures 16
- Cautions for the water drainage lifting pipe 17
- Installation of water drainage pipe 17
- Installation procedures 17
- Install ornament panel on indoor unit 18
- Installation of ornament panel 18
- Installation procedures 18
- Panel limitation board installation 18
- Piping connection 18
- 092 122 19
- Cautions for piping connection 19
- Installation procedures 19
- 4 purging method the refrigerant is r407c 20
- Installation procedures 20
- To use vacuum pump 20
- Connection of outdoor piping 21
- Crimp connection method of connecting line 21
- Electrical wiring 21
- Installation fixing 21
- Installation of drain elbow 21
- Installation procedures 21
- Wiring connection 21
- Wiring method of straight terminal 21
- Wiring methods 1 wiring method of ring terminal 21
- Wiring of indoor unit 21
- Installation procedures 22
- Wiring connection 22
- The followings are not malfuncition 23
- Troubleshooting 23
- Please check the following things about your air conditioner before making a service call 24
- Troubleshooting 24
- Unit fails to start 24
- Failure code 25
- Check and test run 26
- Installation check and test run 26
Похожие устройства
- Haier AB182ACBFA Инструкция по эксплуатации
- Haier AB182ACAEA Инструкция по эксплуатации
- Haier AB282ACAEA Инструкция по эксплуатации
- Haier AB42NACAEA Инструкция по эксплуатации
- Vodotok НСП-600 Инструкция по эксплуатации
- Vodotok НСП-800 Инструкция по эксплуатации
- Vodotok PJm80 Инструкция по эксплуатации
- Vodotok PJm100 Инструкция по эксплуатации
- Vodotok PJWm10H Инструкция по эксплуатации
- Vodotok PJWm15H Инструкция по эксплуатации
- Vodotok XRS20/4-130 Инструкция по эксплуатации
- Vodotok XRS25/4-130 Инструкция по эксплуатации
- Vodotok XRS25/4-180 Инструкция по эксплуатации
- Vodotok XRS32/4-180 Инструкция по эксплуатации
- Vodotok XRS20/6-130 Инструкция по эксплуатации
- Vodotok XRS25/6-130 Инструкция по эксплуатации
- Vodotok XRS25/6-180 Инструкция по эксплуатации
- Vodotok XRS32/6-180 Инструкция по эксплуатации
- Vodotok XRS40/6-180-W Инструкция по эксплуатации
- Vodotok XRS25/8-180-W Инструкция по эксплуатации