Kentatsu KFKD30H0EN1 [27/32] Wiring installation

Kentatsu KFKD70H0EN1 [27/32] Wiring installation
27
KFKD middle static pressure duct

2. Drain test
Before the test, ensure that the drain pipes are smooth and the adapters are sealed.
Newly built rooms should undergo the drain test before the ceiling is laid.
8.6 Wiring installation
CAUTIONS:
The air conditioner should use separate power supply with rated voltage.
The external power supply to the air conditioner should have ground wiring, which is linked to the
ground wiring of the indoor and outdoor unit.
The wiring work should be done by qualified persons according to circuit drawing.
An all-pole disconnection device which has at least 3mm separation distance in all pole and a residual
current device(RCD)with the rating of above 10mA shall be incorporated in the fixed wiring according to
the national rule.
The appliance shall be installed in accordance with national wiring regulations.
Be sure to locate the power wiring and the signal wrings well to avoid cross-disturbance.
Do not turn on the power until you have checked carefully after wiring.
The wiring connection please refers to chapter 5.