9.5. Louver Control
9.5.1. Louver control for cassette type
When power is on, at the same time, louver start initializing toward to close Direction.
During operation, stopping, thermostat off condition, louver angle set manual or auto depend on remote controller setting.
Louver manual setting
Operation mode Display manual
Set 1 Set 2 Set 3 Set 4
Normal 20° 35° 50° 70°
Heating Defrost 10°
Hot start 10°
Thermostat off 20°
Fan 20° 35° 50° 70°
Cooling Normal 20° 35° 50° 70°
(fan) Dew control 50°
Thermostat off 20° 35° 50° 70°
Normal 30°
Dry Dew control 50°
Thermostat off 20° 35° 50° 70°
Operation mode judge 20° 35° 50° 70°
Stop mode
Louver auto setting
Operation Display auto set
AUTO 1 AUTO 2 AUTO 3
A 70° 70° 70°
Normal Sensor B 20° - 70° 20° - 50° 40° - 70°
Heating C 20° 20° 20°
Defrost 10°
Hot start 10°
Thermostat off 20°
Fan 20° - 70° 20° - 50° 40° - 70°
Cooling Normal 20° - 70° 20° - 50° 40° - 70°
(Fan) Dew control 50°
Thermostat off 20° - 70° 20° - 50° 40° - 70°
Normal 30°
Dry Dew control 50°
Thermostat off 20° - 70° 20° - 50° 40° - 70°
Operation mode judge 20° 20° 20°
Stop mode
Temperature range for louver control during heating operation is as follows; decide by indoor heat exchanger temperature.
AUTOBW1 AUTOBW2 AUTOBW3 AUTOBW4
60°C 57°C 30°C 25°C