Sdmo VERSO 50 TRI 40A [4/26] Protection degree ip20

Sdmo VERSO 50 MONO 40A [4/26] Protection degree ip20
VERSO 50-RU-v1.0.18_rev2.docx 33502027401_0_1 Page 2/23
OVERVIEW - MAIN CHARACTERISTICS - INSTALLATION - WIRING
Complete delivered equipment with connecting cables
Protection degree: IP20
References Sizes and Weights:
ATS type
reference
height (mm)
width (mm)
depth (mm)
weight (kg)
single phase 40A (see 3-1 page 19/23)
31614298801NE
280
400
150
10
single phase 100A (see 3-2 page 20/23)
31614298901NE
280
400
150
10
three phases 25A (see 3-3 page 21/23)
31614299001NE
280
400
150
10
three phase 40A (see 3-4 page 22/23)
31614299101NE
280
400
150
10
¾Entraxe of fixation:
The panel must be fixed on the wall like the
picture opposite, with appropriate material.
Be careful, there are 3 meters length cable
between the genset control panel and the ATS.
Section of cables - plug caliber - Installation diagram:
ATS type
Generator
(power plug)
Generator
(control plug)
Mains
(directly on the contactor)
Utilization
(terminal blocks)
32 Amps-3 pins
4 pins 0,75mm²
up to 2 x 6mm² / phase
up to 25mm²
single phase 100A 32 Amps-3 pins 4 pins
0,75mm² up to 1 x 25mm² / phase
up to 50mm²
16 Amps-5 pins
4 pins 0,75mm²
up to 1 x 6mm² / phase
up to 10mm²
32 Amps-5 pins
4 pins 0,75mm²
up to 1 x 6mm² / phase
up to 16mm²
table 1
See complete electrical
diagrams pages 19,20,21,22