VTS VENTUS S-type SVS-100 [11/21] Draining out condensate
![VTS VENTUS S-type SVS-85 [11/21] Draining out condensate](/views2/1894973/page11/bgb.png)
11
Fig.10. Example of a feeding water exchanger
4.4. Draining out condensate
The outlet condensate connections, led outside the AHU's casing are assembled in the drain plates of glycol,
cross-flow and rotary exchangers (the diameter of drain pan connection pipe is 32mm).
Siphons, which are designed to drain out condensed water from the exchangers at different pressure of the
section and environment, should be connected to the drain connections.
Drain siphons or siphon parts for SVS AHUs are not supplied as a standard delivery.
Siphon’s usable „H" height depends on the pressure difference between the AHU section, where the
condensate is drained during the operation and under the ambient pressure. „H" dimension is provided in
mm and must be higher than the pressure difference expressed in mmH
2
O.
Table 3. Siphons' operational height
No.
Total fan's pressure
[Pa]
Size
H [mm]
1.
< 600
60
2.
600-1000
100
Fig.11. Ball siphon
It is allowable to join together siphons of various units with one drain interceptor provided that the interceptor is
equipped with air-escape. Before starting the AHU, fill the siphon with water.
It is also possible to use a special type of mechanical pump to force the removal of condensate.
Содержание
- Operation and maintenance manual 1
- Ventus s type air handling units 1
- Attention in order to ensure proper condensate elimination this air handling unit requires accurate levelling use a spirit level tool when installing 2
- Application and design 4 3
- Information 21 3
- Introduction 4 3
- Mounting connection to unit related systems 7 3
- Operation and maintenance 18 3
- Preparation for start up 16 3
- Safety instructions 20 3
- Start up and adjustment 17 3
- Table of contents 3
- Transport and storage 6 3
- Application and design 4
- Introduction 4
- Ventus s type air handling units 4
- Fig example of suspended ahus type svs 35 100 5
- Tab dimensions of ahus type svs 35 100 tab dimensions of ahus type svs 35 100 5
- This type of suspended ahus is available only in the right hand rh configuration fig 5
- Transport and storage 6
- Ventus s type air handling units 6
- Mounting connection to unit related systems 7
- Suspending the ventus s type unit 7
- Ventus s type air handling units 8
- Connecting the ventilation ducts 9
- Connection of coolers 10
- Connection of coolers should be done in such a way so as not to allow for stresses exchanger s connections which may result in mechanical damages or leakages the pipeline weight and thermal stresses cannot be passed onto the exchanger s connections depending on local conditions please use the compensation at the inlet and outlet of the pipeline system in order to level the pipeline s linear expansion during assembly of the supply system to the cooler equipped with the screwed connections counter the exchanger s connection with additional wrench fig 10
- Examples of connecting inlet and outlet pipelines for various ahu versions shown in the picture 10
- Fig securing the screwed connections of the exchanger 10
- Inlet and outlet exchanger s connections should be connected so that the exchanger operates in a counter current way streamwise operation results in the lower average discrepancy of temperatures which influences the exchanger s performance 10
- Table 2 diameters of coolers connection pipes 10
- The supply system should be planned in such a way so that it does not collide with the other ahu sections the way of connecting the exchangers with the supply system should allow for an easy pipeline disassembly in order 10
- To remove the exchanger from the ahu during maintenance and service operations 10
- Ventus s type air handling units 10
- Vts reserves the right to implement changes without prior notice 10
- Draining out condensate 11
- Electric connection 12
- Fan sets 12
- Ventus s type air handling units 12
- Ventus s type air handling units 14
- Automatic control 15
- Electrical system 16
- Fan unit 16
- Filters 16
- Preparation for start up 16
- Ventus s type air handling units 16
- Measurement of the air quantity and ahu output adjustment 17
- Start up and adjustment 17
- Operation and maintenance 18
- Ventus s type air handling units 18
- Dampers 19
- Filters 19
- Cooler 20
- Fan unit 20
- Safety instructions 20
- Test measurements 20
- Ventus s type air handling units 20
- Information 21
Похожие устройства
- VTS VENTUS S-type SVS-100 Брошюра
- VTS VENTUS S-type SVS-100 Сертификат
- Abat ШС‑32‑1‑03 Технические данные
- Abat ШС‑32‑1‑03 Инструкция по эксплуатации
- Abat ШС‑32‑2В‑01 Технические данные
- Abat ШС‑32‑2В‑01 Инструкция по эксплуатации
- Abat ШС‑32‑2В‑03 Технические данные
- Abat ШС‑32‑2В‑03 Инструкция по эксплуатации
- Abat ШС‑32‑2Г‑01 Инструкция по эксплуатации
- Abat ШС‑32‑2Г‑03 Инструкция по эксплуатации
- Abat ШС‑32‑1‑02 Технические данные
- Abat ШС‑32‑1 Технические данные
- Abat ШС‑32‑2В‑02 Технические данные
- Abat ШС‑32‑2В Технические данные
- Abat ШС‑32‑2Г‑02 Технические данные
- Abat ШС‑32‑2Г Технические данные
- Abat КВЭ‑15 Технические данные
- Abat КВЭ‑15 Инструкция по эксплуатации
- Abat КВЭ‑30 Инструкция по эксплуатации
- Abat КВЭ‑30 Технические данные