Berg BACC30-T1-230 [24/72] Parameters for mixing circuit

Berg BACC30-T1-230 [24/72] Parameters for mixing circuit
24 | Service manual
EN
Para-
meter
Function Parameter description Setting range Default
value
S1.5 DISPLAY
ORIENTATION
Setting of display orientation. 0 - REGULAR
1 - ROTATED
180°
0
S1.9 ANTI-BLOCK
FUNCTION FOR
PUMP AND
VALVE
All outputs that haven’t been
activated in the last week are
activated on Friday at 20:00 for
60 seconds.
0- OFF
1- ON
0
S1.17 SENSOR T1
CALIBRATION
Correction of displayed measured
temperature for sensor T1.
-5 ÷ 5 K 0
S1.18 SENSOR T2
CALIBRATION
Correction of displayed measured
temperature for sensor T2.
-5 ÷ 5 K 0
Para-
meter
Function Parameter description Setting range Default
value
S2.1 MIN. SETPOINT
TEMPERATURE
IN HEATING
MODE
Setting of minimal allowed setpoint
temperature in heating mode. Setpoint
temperature cannot be adjusted lower
as with this parameter.
5 ÷ 70 °C 50 °C
S2.2 MAX. SETPOINT
TEMPERATURE
IN HEATING
MODE
Setting of maximal allowed setpoint
temperature in heating mode. Setpoint
temperature cannot be adjusted higher
as with this parameter.
10 ÷ 95 °C 70 °C
S2.3 MIN. SETPOINT
TEMPERATURE
IN COOLING
MODE
Setting of minimal allowed setpoint
temperature in cooling mode. Setpoint
temperature cannot be adjusted lower
as with this parameter.
10 ÷ 25 °C 15 °C
S2.4 MAX. SETPOINT
TEMPERATURE
IN COOLING
MODE
Setting of maximal allowed setpoint
temperature in cooling mode. Setpoint
temperature cannot be adjusted higher
as with this parameter.
15 ÷ 35 °C 30 °C
S2.7 BACKLASH OF
MIXING VALVE
Setting of mixing valve running time to
compensate the backlash of actuator
and mixing valve assembly, which oc-
cours by change of rotation direction.
0 ÷ 5 s 1
S2.8 MIXING VALVE
P - CONSTANT
Setting of mixing valve position cor-
rection intensity. Smaller value means
shorter movements, higher value
means longer movements,
0,5 ÷ 2,0 1
PARAMETERS FOR MIXING CIRCUIT:
CONTROLLER PARAMETER

Содержание

Скачать