| 27Service manual
EN
Para-
meter
Function Parameter description Setting range Default
value
S3.4 SYSTEM
PROTECTION
IN COOLING
MODE -
SENSOR T2
Setting of controller respond in case
if T2 sensor is installed. If T2 tempera-
ture is lower as paremeter S3.5, the
controller fully closes the valve. If T2 is
higher as parameter S3.6, the control-
ler fully opens the valve.
0 - Sensor T2 is not used for system
protection.
1- Only minimal temperature is
respected for system protection (pa-
rameter S3.5).
2- Only maximal temperature is
respected for system protection (pa-
rameter S3.6).
3- Minimal and maximal temperature
is respected for system protection
(parameter S3.5 in S3.6).
0- WITHOUT
1- TMIN
2- TMAX
3- TMIN IN
TMAX
3
S3.5 MIN.SYSTEM
TEMPERATURE
IN COOLING
MODE
Setting of minimal temperature at
which the controller fully closes the
valve.
60 ÷ 160 °C 15
S3.6 MAX. SYSTEM
TEMPERATURE
IN COOLING
MODE
Setting of maximal temperature at
which the controller fully opens the
valve.
60 ÷ 160 °C 30
CONTROLLER PARAMETER