Legrand MegaLine Rack 1250 Инструкция по эксплуатации онлайн

87045 LIMOGES Cedex
Telephone : (+33) 05 55 06 87 87 - Fax : (+33) 05 55 06 88 88
TABLE OF CONTENTS Page
1. General features .................................... 1
2. Technical features .................................2
3 103 79
MegaLine Rack 1250
The Legrand UPS MegaLine Rack 1250 model is a UPS using high
frequency PWM technology, On Line Double Conversion type,
solid neutral, modular architecture, with the possibility of N+X
redundant configuration, Rated Power 1,250 VA – 875 W, equipped
with valve-regulated hermetic-type accumulator batteries,
contained inside the UPS in a specific compartment or in one or more
external cabinets, sized to guarantee a minimum autonomy
of 11 minutes when 80% charged.
1.1 Modularity
The MegaLine Rack UPS has a modular architecture, it is composed
of identical modules that, conceptually operating in parallel, compose
the power section (1250VA power modules) and the group
of accumulators (battery modules) of the UPS.
These modules are contained inside the UPS and have identical
functions.
The power modules are composed of the functional blocks listed
below:
• Rectifier/PFC
• Inverter
• Booster
• BatteryCharger
The battery modules on the other hand, are composed of a series
of batteries, protected accordingly by fuses in series.
1.2 Expandability
ThemodularityoftheUPSallowsforpowerand/orback-uptime
expansion, upgrading on site, without the need for calibration, settings,
factory changes and in any case without the use of dedicated tools.
1.3 Redundancy
The modular UPS is configurable as an N+X redundant power system,
with 1,250 VA modules, contained in the UPS cabinet,
with suitable mechanical latches and dedicated and pre-arranged
electric connections.
Redundancy is achieved by an architecture based on the concept
of “load sharing”.
1.4 Architecture
The system uses distributed parallel architecture, in other words all
of the power modules share the load (load sharing) so that none of
the power modules remain inactive or in stand-by, thus ensuring total
continuity to the power supply of the loads, even in case of failure
(with suitable redundant sizing). The modular architecture offers the
possibility of supplying the load with energy even if the inverter of a
power module shuts down (if there are two or more modules).
The rated power that can be delivered by the sum of the working
modules will always be available to the user who can operate at a
reduced load or, with a redundant configuration, at the normal load.
1. GENERAL FEATURES
1.5 Bypass
A by-pass circuit automatically transfers the load directly to the
primary network without interrupting the power supply, in conditions
of overload, overheating, continuous voltage outside of the tolerances
and inverter fault.
A diagnostic and shutdown software (UPS Communicator), if installed
accordingly on a PC connected to the UPS, allows you to access all of
the MegaLine operating data, regulate and set special functions (such
as the display screen) and control the shut down of Windows and
Linux operating systems.
An optional software (UPS SuperviSor) provides hierarchical
multiserver shutdown and remote UPS management for any operating
system in a heterogeneous network (Windows, Novell, Linux and the
most common Unix).
MegaLine Rack is managed by a microprocessor and is capable
of displaying measurements, alarms and operating modes with a liquid
crystal control panel and high luminosity signals.
The UPS is capable of carrying out the following measurements and
displaying the values directly on the display:
Input
Current:
• Effectivevalue
• Peakvalue
• Crestfactor
Voltage:
• Effectivevalue
Power:
• Apparent
• Active
Power factor
Frequency
Output
Current:
• Effectivevalue
• Peakvalue
• Crestfactor
Voltage:
• Effectivevalue
Power:
• Apparent
• Active
Power factor
Frequency
Batteries
• AdditionalBatteryModules
• AdditionalBatteryChargers
• Batteryoperationtime
• Numberofdischargecycles
• Residualcapacity
• Batteryvoltage
Various
• Internaltemperature
• Externaltemperature
Data log
• Bypassoperation
• Overheating
• Numberofswitchesperbat-
tery
• Numberoftotaldischarges
Time:
• Batteryoperation
• Networkoperation
Datasheet:UPS-LGR-0010/GB 01/09/2012Update:01/09/2012
1/2
Содержание
- General features 1
- Megaline rack 1250 1
- Table of contents page 1
- 09 2012 2
- Batteries capacity thresholds max durationperbattery max durationperbatteryafter 2
- By pass enable forced operationsensitivity off linemode loadwaitingmode 2
- Continued 2
- Datasheet ups lgr 0010 gb update 01 09 2012 2
- En62040 2 electromagneticcompatibility emc requirements en62040 3 methodofspecifyingtheperformanceandtest 2
- Enablebatterytest enableauto restart 2
- General features 2
- Input enablesynchronisation extendedsynchronisation 2
- Interval 2
- Megaline rack 1250 2
- Neutral sensor enable ignoreduringoperation 2
- Operator access areas 2
- Output voltage frequency n xredundancy 2
- Requirements 2
- Technical features 2
- The reserve capacity threshold 2
- The static megaline rack ups has the ce marking pursuant to directives73 23 93 68 89 336 92 31 93 68andisdesignedandbuilt in compliance with the following standards en62040 1 generalandsafetyrequirementsforupsusedin 2
- The ups also allows the following adjustments to be made through the display 2
Похожие устройства
- Legrand MegaLine Rack 2500 Инструкция по эксплуатации
- Legrand MegaLine Rack 2500 Инструкция по эксплуатации
- Legrand MegaLine Rack 3750 Инструкция по эксплуатации
- Legrand MegaLine Rack 3750 Инструкция по эксплуатации
- Legrand MegaLine Rack 5000 Инструкция по эксплуатации
- Legrand MegaLine Rack 5000 Инструкция по эксплуатации
- Legrand TRIMOD HE 10 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 10 kVA Технические характеристики
- Legrand TRIMOD HE 10 kVA Технические характеристики
- Legrand TRIMOD HE 15 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 15 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 15 kVA Технические характеристики
- Legrand TRIMOD HE 20 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 20 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 20 kVA Технические характеристики
- Legrand TRIMOD HE 30 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 30 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 30 kVA Технические характеристики
- Legrand TRIMOD HE 40 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 40 kVA Инструкция по эксплуатации