Legrand MegaLine Rack 1250 [2/2] Megaline rack 1250
![Legrand MegaLine Rack 1250 [2/2] Megaline rack 1250](/views2/1165512/page2/bg2.png)
Datasheet:UPS-LGR-0010/GB Update:01/09/2012
3 103 79
MegaLine Rack 1250
01/09/2012
2/2
Manufacturing specifications
Maximum weight
23.5 kg
(for a back-up time of 11’ – 80% of the load)
Maximum dimensions (W×L×H)
483x630x266mm(19”Rack–6units)–back-
up time 11’- 80% of the load
Type of switching High frequency PWM
Rectifier/booster/invertertechnology MOSFET
Interfaces
1x RS232 serial port +
2xLogic Contact ports
Noise level measured at 1 meter <40dBA
Degree of protection IP21
Installed power boards 1
Free power expansion slots 3
Installed battery kits 1
Free uptime expansion slots 3
Battery features
Type of battery Lead-acid, sealed, maintenance-free
Unitary capacity 9Ah(12V)
UPSbattery/batterymodulevoltage 36 V max. (series of 3*12V)
Batterymoduleprotection 2 fuses for each battery module
Output features (battery operation)
Rated output voltage 230 V (adjustable by 1 V intervals)
Tolerance on the output voltage
Static ± 1%;
Dynamic (0-100%; 100-0%) ± 1%
Output frequency 50 Hz or 60 Hz ± 1%
Rated/activeoutputpower 1,250VA/875W
Total harmonic distortion of the output voltage
on non-linear rated load, P.F.=0.7
< 1 %
Overload capacity:
•for15seconds
160%
Input features
Rated input voltage 230 V
Input voltage interval
From 184 V to 264 V with rated load
From 110 V to 264 V at 50% of the rated load
Input frequency
50 Hz or 60Hz
(autosensing or selected by the user)
Total harmonic distortion of the input current
(THDI
in
)
< 3% at 100% of the rated load
Power factor >0.99from20%to100%oftheratedload
Inrush current At most 100% of the load current
Output features (network operation)
Rated output voltage 230 V (adjustable by 1 V intervals)
Rated/activeoutputpower 1,250VA/875W
Tolerance on the output voltage
Static ± 1%;
Dynamic (0-200%; 200-0%) ± 1%
Total harmonic distortion of the output voltage
Linear load < 0.5 %;
Non-linear load < 1 %
Rated output frequency
50 Hz or 60 Hz
(autosensingand/orselectedbytheuser)
Tolerance on the output frequency
Synchronised to the input frequency;
± 1% when not synch.
Crest factor on the output current 3.5:1
Overload capacity:
•foratleast1second
•foratleast5seconds
•foratleast30seconds
300% without the operation of the automatic bypass
200% without the operation of the automatic bypass
150% without the operation of the automatic bypass
2. TECHNICAL FEATURES
General Features
Type of operation On line double conversion
UPS Structure
Modular, Expandable, N+X Redundant
with 1,250 VA power modules,
contained in a single cabinet
Neutral Connectivity Solid neutral
Wave shape in networked operation Sinusoidal
Wave shape in battery operation Sinusoidal
Type of bypass Static and electromechanical
Switching time None
1. GENERAL FEATURES (continued)
Output
• Voltage
• Frequency
• N+Xredundancy
Input
• Enablesynchronisation
• Extendedsynchronisation
interval
By-Pass
• Enable
• Forced
• Operationsensitivity
• Off-linemode
• Loadwaitingmode
Neutral sensor
• Enable
• Ignoreduringoperation
Batteries
• Capacity
• Thresholds
• Max.durationperbattery
• Max.durationperbatteryafter
the reserve capacity threshold
• Enablebatterytest
• Enableauto-restart
The UPS also allows the following adjustments to be made through the
display:
The Static MegaLine Rack UPS has the CE marking, pursuant to
Directives73/23,93/68,89/336,92/31,93/68andisdesignedandbuilt
in compliance with the following standards:
• EN62040-1“GeneralandsafetyrequirementsforUPSusedin
operator access areas”
• EN62040-2“Electromagneticcompatibility(EMC)requirements”
• EN62040-3“Methodofspecifyingtheperformanceandtest
requirements”
Содержание
- General features 1
- Megaline rack 1250 1
- Table of contents page 1
- 09 2012 2
- Batteries capacity thresholds max durationperbattery max durationperbatteryafter 2
- By pass enable forced operationsensitivity off linemode loadwaitingmode 2
- Continued 2
- Datasheet ups lgr 0010 gb update 01 09 2012 2
- En62040 2 electromagneticcompatibility emc requirements en62040 3 methodofspecifyingtheperformanceandtest 2
- Enablebatterytest enableauto restart 2
- General features 2
- Input enablesynchronisation extendedsynchronisation 2
- Interval 2
- Megaline rack 1250 2
- Neutral sensor enable ignoreduringoperation 2
- Operator access areas 2
- Output voltage frequency n xredundancy 2
- Requirements 2
- Technical features 2
- The reserve capacity threshold 2
- The static megaline rack ups has the ce marking pursuant to directives73 23 93 68 89 336 92 31 93 68andisdesignedandbuilt in compliance with the following standards en62040 1 generalandsafetyrequirementsforupsusedin 2
- The ups also allows the following adjustments to be made through the display 2
Похожие устройства
- Legrand MegaLine Rack 2500 Инструкция по эксплуатации
- Legrand MegaLine Rack 2500 Инструкция по эксплуатации
- Legrand MegaLine Rack 3750 Инструкция по эксплуатации
- Legrand MegaLine Rack 3750 Инструкция по эксплуатации
- Legrand MegaLine Rack 5000 Инструкция по эксплуатации
- Legrand MegaLine Rack 5000 Инструкция по эксплуатации
- Legrand TRIMOD HE 10 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 10 kVA Технические характеристики
- Legrand TRIMOD HE 10 kVA Технические характеристики
- Legrand TRIMOD HE 15 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 15 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 15 kVA Технические характеристики
- Legrand TRIMOD HE 20 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 20 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 20 kVA Технические характеристики
- Legrand TRIMOD HE 30 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 30 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 30 kVA Технические характеристики
- Legrand TRIMOD HE 40 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 40 kVA Инструкция по эксплуатации