Legrand ARCHIMOD HE 60 kVA [3/14] Reference standards 14
![Legrand ARCHIMOD HE 60 kVA [3/14] Reference standards 14](/views2/1165545/page3/bg3.png)
3 di 14
5! Control Panel and Display ................................................................... 10!
5.1! CONTROLS .............................................................................................................................................. 11!
5.2! MEASUREMENTS ...................................................................................................................................... 11!
5.3! ADJUSTMENTS ......................................................................................................................................... 11!
5.4! SIGNALS AND ALARMS ............................................................................................................................. 12!
5.5! MISCELLANEOUS EQUIPMENT ................................................................................................................... 12!
5.5.1! INTERFACES ......................................................................................................................................................... 12!
5.5.2! E.P.O.(EMERGENCY POWER OFF) ........................................................................................................................ 12!
5.5.3! RS232 SERIAL PORT ........................................................................................................................................... 12!
6! Technical specifications ................................................................. 13!
6.1! GENERAL SPECIFICATIONS ....................................................................................................................... 13!
6.2! INPUT ...................................................................................................................................................... 13!
6.3! OUTPUT WITH MAINS (AC-AC) ................................................................................................................. 13!
6.4! OUTPUT IN BATTERY RUN (DC-AC) .......................................................................................................... 13!
6.5! BATTERY ................................................................................................................................................. 14!
6.6! ENVIRONMENTAL SPECS ........................................................................................................................... 14!
6.7! MECHANICAL AN MICHELLANEOUS ........................................................................................................... 14!
1! REFERENCE STANDARDS .................................................................... 14!
Содержание
- For three phase ups on line double conversion vfi 1
- Kva 60 kw 1
- Tender technical specification 1
- Description of the system 6 2
- General requirements 4 2
- Generali specifications 4 2
- Operating principle 8 2
- Control panel and display 10 3
- Reference standards 14 3
- Technical specifications 13 3
- General requirements 4
- Generali specifications 4
- X n p p 5
- Description of the system 6
- Bypass activation sensitivity adjustment 8
- Inverter stopping 8
- Operating principle 8
- Overload 8
- After a blackout 9
- Cold start 9
- Inverter stopping in a power module 9
- Maintenance bypass 9
- Smart eco mode 9
- Start up on bypass 9
- Asynchronous operation 10
- Control panel and display 10
- Frequency converter 10
- Genset 10
- Hot plug hot swap 10
- Operation with a genset or as a frequency converter 10
- Adjustments 11
- Buzzer silencer 11
- Controls 11
- Enter the operating parameters ref sect 5 adjustments 11
- Functions and quitting 11
- Keyboard to browse the menus on the display set parameters confirming the selected 11
- Measurements 11
- Select the language in which the messages are given 11
- Set running parameters 11
- Shutdown in an emergency the button must remain depressed for at least 3 seconds 11
- The ups can manage the following measurements and show the relevant values on the display 11
- The ups has the following controls 11
- The will ups allow the following adjustments to be made and shown on the display 11
- Ups secure powering protection against accidental powering 11
- Ups stopping to prevent accidental power offs while allowing the ups to be quickly 11
- E p o emergency power off 12
- Interfaces 12
- Miscellaneous equipment 12
- Rs232 serial port 12
- Signals and alarms 12
- General specifications 13
- Item data 13
- Output in battery run dc ac 13
- Output with mains ac ac 13
- Technical specifications 13
- En 62040 1 general and safety requirements for ups used in operator access areas 14
- En 62040 2 electromagnetic compatibility requirements emc 14
- En 62040 3 performance requirements and test methods 14
- Reference standards 14
- The static uninterruptible power system must be designed and produced in compliance with the following international standards 14
- The ups manifacturer company must have iso9001 certification for development production and services 14
- The ups must have ce marking in accordance with european directives 73 23 93 68 89 336 92 31 the ups must have ce marking in accordance with european directives 73 23 93 68 89 336 92 31 93 68 14
Похожие устройства
- Legrand ARCHIMOD HE 80 kVA Инструкция по эксплуатации
- Legrand ARCHIMOD HE 80 kVA Инструкция по эксплуатации
- Legrand ARCHIMOD HE 80 kVA Технические характеристики
- Legrand ARCHIMOD HE 100 kVA Инструкция по эксплуатации
- Legrand ARCHIMOD HE 100 kVA Инструкция по эксплуатации
- Legrand ARCHIMOD HE 100 kVA Технические характеристики
- Legrand ARCHIMOD HE 120 kVA Инструкция по эксплуатации
- Legrand ARCHIMOD HE 120 kVA Инструкция по эксплуатации
- Legrand ARCHIMOD HE 120 kVA Технические характеристики
- Legrand Keor LP 1000 Инструкция по эксплуатации
- Legrand Keor LP 1000 Технические характеристики
- Legrand Keor LP 2000 Инструкция по эксплуатации
- Legrand Keor LP 2000 Технические характеристики
- Legrand Keor LP 3000 Инструкция по эксплуатации
- Legrand Keor LP 3000 Технические характеристики
- Legrand Daker DK 10000 – Inverter 3-1 Инструкция по эксплуатации
- Legrand Daker DK 10000 – Inverter 3-1 Инструкция по эксплуатации
- Legrand Daker DK 4500 Инструкция по эксплуатации
- Legrand Daker DK 4500 Инструкция по эксплуатации
- Legrand Daker DK 4500 – Inverter Инструкция по эксплуатации