Legrand Keor S 10000 [2/2] Keor s 10000

Legrand Keor S 10000 [2/2] Keor s 10000
Data sheet: UPS-LGR-0089/GB Update: 03/11/2014
2. TECHNICAL FEATURES (continued)
03/11/2014
2/2
Output with Mains (AC-AC)
Nominal Voltage 220V, 230V, 240V mono phase + neutral + PE
Nominal Power 10.000 VA
Active Power 9.000 W
Voltage variation (static) ± 1%
THDv on nominal power (linear load) < 3%
Frequency 50 Hz or 60 Hz (selectable)
Frequency tolerance ± 0,2% Synchronized with bypass frequency
Current Crest Factor 2,5:1 accordingly to IEC 62040-3
Overload capability:
* 2min
* 30sec
120% load rate with no bypass transfer
150% load rate with no bypass transfer"
Output with Mains (DC-AC)
Nominal Voltage 220V, 230V, 240V mono phase + neutral + PE
Nominal Power 10.000 VA
Active Power 9.000 W
Voltage variation (static) ± 1%
THDv on nominal power (linear load) < 2%
Frequency 50 Hz or 60 Hz (selectable)
Frequency tolerance ± 0,01% free run
Current Crest Factor 2,5:1 accordingly to IEC 62040-3
Overload capability:
* 2min
* 30sec"
120% load rate
150% load rate
Battery features
Type Lead Acid, sealed, maintenance free VRLA
Internal Battery Capacity ¹ 12 Ah (12V)
Nominal UPS Battery Voltage 240 Volt DC
Max. number of possible internal battery 20pcs
Standard Charging Current 1,6 A
Additional Charger
Yes, Optional - External, mountable on battery
cabinet
Additional Charger Capacity 2,5A
Environmental Specifications
Noise level 1m < 52dBA
Operating temperature range from 0°C to +40°C
Stock temperature range from -20°C to +50°C
Humidity range 20-95% not condensing
Protection degree IP31
Manufacturing Specifications
Net Weight without batteries ² 60 kg
Net Weight with Int. Transformer 126 kg
Dimensions (WxHxD) 275 x 716 x 776 mm
Colour RAL 7016
Communication Interface
1 serial port RS232, 1 smart slot (for optional
internal SNMP), 1 EPO, 1 GENSET
Input/Output connections 1P + N + PE
Input/Output Circuit Breaker 63A / 50A
1
When used with internal transformer, batteries must be used in separate cabinet
General Features
UPS Topology On line double conversion
Architecture of the UPS
Stand alone, transformerless, On-Site Paralleling
In/Out phase Configuration Mono phase-Mono phase
Neutral Neutral Passing through
Switching Technology IGBT
Backfeed Protection Internal, standard
Output wave form on mains operation Sinusoidal
Output wave form on battery operation Sinusoidal
Standards EN 62040-1, EN 62040-2, EN 62040-3
Bypass
Nominal Voltage 230 V mono phase + neutral + PE
Voltage Range ±10% (adjustable)
Frequency ±3Hz (adjustable)
Bypass type Static and electro-mechanic
Transfer time Zero
Manual Bypass Built-in
Input Features
Nominal Voltage 230 V mono phase + neutral + PE
Voltage Range 195V-280V Ph-N full load
Frequency 45 - 65Hz
THDi < 6% at full load
Power Factor > 0.99
2
Total weight depends on the quantity of the installed batteries according to the required autonomy
3. REAR PANEL DRAWING
3 101 31 - 3 101 35
Keor S 10000
Long backup time table
KEOR S
UPS
Items
Battery
cabinet
Items
Backup time (min)
50%
load
60%
load
70%
load
80%
load
90%
load
full
load
10000 VA
3 101 31
3 107 44 45 30 27 25 20 18
3 107 45 70 60 50 40 32 30
2 x 3 107 45 120 100 85 73 65 60
3 101 35
3 107 44 18 13 10 8 6 5
3 107 45 45 30 27 25 20 18
2 x 3 107 45 95 70 65 60 50 45