1. General Mode:
a. Press the “Display-Toggle” button to check the status of the UPS status:
b. Press and hold the “Display-Toggle” button for 4 seconds,
If the machine is in the Battery Mode with active alarm, it will become silent.
If the machine is in the Line Mode, a self- diagnostic test will take place.
c. If the “Display-Toggle” button remains untouched for over 30 seconds, the LCD backlight will turn off
automatically.
2. Set-up Mode
Step 1: Hold the “Display-Toggle” button for 10 seconds to enter the UPS Set-Up Mode.
Step 2: By pressing the Display toggle, users can switch between setup functions. Some User Configurable
functions are as follows:
a. Delay Time: The time delay between switching from Battery Mode to Line Mode. There are 9 different
settings. The default setting is 0 minutes.
b. Battery Pack Numbers: This function provides the estimated UPS runtime using various numbers of
battery packs. The default setting is 0.
c. Voltage Mode:The AC output voltage on battery mode.There are 3 different settings(220,230,240).
d. Static Frequency Tolerance: There are 4 settings (1,2,4,6%), and the default setting is +/-6%. Functional
description: The setting may be adjusted to the quality of the electricity in use.
e. Slew rate: Also known as Dynamic Frequency Tolerance. There are 5 different settings (0.25,0.5,1,2,4
Hz/Sec). The fault value is 4Hz/sec. Functional Description: “Slew Rate” indicates the tolerance of a
device in accepting frequency variance. Lower “Slew Rate” results in less tolerance but better protection
for the connected load and vice versa.
f. Low Battery Shutdown Voltage: This function will adjust the UPS shutdown point according to the
battery’s remaining capacity.
These programmable items are sorted by unit as in the following table
Step 3: Press and hold the display-toggle for 4 seconds. When the icons blink, the value of each item is
changed by slightly pressing the toggle.
Item
Unit
1 Input Voltage V
2 Output Voltage V
3 Output Frequency Hz
4 Load Kw
5 Estimate Run Time Min
6 Load Capacity %
7 Battery Capacity %
8 Centigrade
9 Fahrenheit
Items
Unit
Delay Time Min
Battery Pack Numbers A
Voltage Mode (220/230/240) V
Static Frequency Tolerance %
Slew Rate Hz
Low Battery Shutdown Voltage V
Firmware Version None