Alarm Contact
The Moxa EtherDevice Switch has one Alarm Contact located on the top
panel. For detailed instructions on how to connect the Alarm Contact
power wires to the two middle contacts of the 6-contact terminal block
connector, see the Wiring the Alarm Contact section on page 6. A
typical scenario would be to connect the Fault circuit to a warning light
located in the control room. The light can be set up to switch on when a
fault is detected.
The Alarm Contact has two terminals that form a Fault circuit for
connecting to an alarm system. The two wires attached to the Fault
contacts form an open circuit when (1) EDS has lost power from one of
the DC power inputs, or (2) one of the ports, for which the corresponding
PORT ALARM DIP switch is set to ON, is not properly connected.
If neither of these two conditions occurs, the Fault circuit will be closed.
DIP Switch Settings
The default setting for each DIP switch is OFF.
The following table explains the effect of setting
the DIP switches to the ON positions.
DIP Switch
Setting
Description
BSP
ON
Enables broadcast storm protection
OFF
Disables broadcast storm protection
----
refers to Jumbo
Frame
ON
Enables jumbo frame function
OFF Disables jumbo frame function
PORT Alarm
ON
Enables the corresponding PORT Alarm. If
the port’s link fails, the relay will form an
open circuit and the fault LED will light up.
OFF
Disables the corresponding PORT Alarm.
The relay will form a closed circuit and the
Fault LED will never light up.
ATTENTION
To actively update DIP switch settings, power off and then power
on the EDS.