ATTENTION
Safety First!
Be sure to disconnect the power cord before installing and/or
wiring your Moxa EtherDevice
Router.
Calculate the maximum possible current in each power wire and
common wire. Observe all electrical code
s dictating the
maximum current allowable for each wire size.
If the current goes above the maximum ratings, the wiring could
overheat, causing serious damage to your equipment.
Please read and follow these guidelines:
Use separate paths to route wiring for power and devices. If power
wiring and device wiring paths must cross, make sure the wires are
perpendicular at the intersection point.
NOTE: Do not run signal or communications wiring and power wiring
through the same wire conduit. To avoid interference, wires with
different signal characteristics should be routed separately.
You can use the type of signal transmitted through a wire to
determine which wires should be kept separate. The rule of thumb is
that wiring sharing similar electrical characteristics can be bundled
together
You should separate input wiring from output wiring
We advise that you label the wiring to all devices in the system.
Grounding the Moxa EtherDevice Router
Grounding and wire routing help limit the effects of noise due to
electromagnetic interference (EMI). Run the ground connection from the
ground screw to the grounding surface prior to connecting devices.
ATTENTION
This product is intended to be mounted
to a well-grounded
mounting surface such as a metal panel.