ioLogik E4200 Utilities
3-11
Administrator Functions
For full access to all configuration options, log in as administrator from the Adaptor Settings tab. This is
required whenever you start up ioAdmin or boot up/restart the ioLogik E4200. When you install the ioLogik
E4200 for the first time, the password will be blank; in this case, click on Login to proceed.
Additional functions will be available after logging in, including the following new tabs:
Network
Firmware Update
Click&Go Logic
Watchdog
Active Tags
ATTENTION
You must log in to access administrator functions, including Network, Communication Watchdog Timer, and
Firmware Update tabs. If you forget the password, you may hold down the ioLogik’s reset button to clear the
password and load factory defaults.
This will result in the loss of all configuration settings and your
Click&Go Logic
Active I/O messaging program!
When making configuration changes, you will need to click on Update or Apply to save the changes. Some
changes will require a restart of the ioLogik I/O system in order to take effect, and you will be given the option
to restart the computer if necessary.
I/O Configuration Tab (Administrator)
When logged on as administrator, click on an IO Module figure in the I/O Configuration tab or click the
module name displayed on the Navigation Panel, and then double click on a channel to configure that channel’s
settings. A window will open with Modbus Address, I/O status, and Config options (for output modules only) for
that module.
Modbus Address
This sub-tab includes a part for Address and another for Module Information. The Address section shows
your channel’s Modbus type: Discrete Input, Coil, or Register. Module Information allows you to check the
module firmware version.