Frico acch15wl [23/56] Ac corinte

Frico acch15wl [23/56] Ac corinte
GB
23
AC Corinte
protect against overheating. This will reset
automatically once the motor has cooled.
Fan replacement
1. Determine which of the fans is not
functioning.
2. Disconnect the cables to the relevant fan.
3. Remove the screws securing the fan and lift
the fan out.
4. Install the new fan in reverse order to the
above.
Changing the electric coil/battery
1. Mark and disconnect the cables to the
electric coil/battery.
2. Remove the mounting screws securing the
electric coil/battery in the unit and lift the
electric coil/battery out.
3. Install the new electric coil/battery in
reverse order to the above.
Troubleshooting
If the fans are not working or not blowing
enough, check the following:
• Operating power supply to the unit;
check fuses, circuit-breaker, time
switch/thermostat (if any) that starts
and stops the unit.
• That the speed regulator is correctly
set.
• That any position limit switch is
working.
• That the thermal safety cut-out for the
motors has not been deployed.
• That the intake grille/filter is not dirty.
If there is no heat, check the following:
• Check that the settings for the
thermostat, switches etc. are set so that
the unit can produce heat.
For units with electrical heating, also check
the following:
• Power supply to electric heater coil;
check fuses and circuit-breaker (if
any).
• That the overheat protection has not
been deployed.
For units with water coil, also check the
following:
• That the water coil is bled.
• That there is a sufficient water flow.
• That the incoming water is sufficiently
hot.
If the error cannot be fixed, please contact a
qualified service technician.
Residual current circuit breaker
(applies to units with electric heater)
When the installation is protected by means
of a residual current circuit breaker, which
trips when the appliance is connected,
this may be due to moisture in the heating
element. When an appliance containing a
heater element has not been used for a long
period or stored in a damp environment,
moisture can enter the element.
This should not be seen as a fault, but is
simply rectified by connecting the appliance
to the mains supply via a socket without a
safety cut-out, so that the moisture can be
eliminated from the element. The drying
time can vary from a few hours to a few days.
As a preventive measure, the unit should
occasionally be run for a short time when
it is not being used for extended periods of
time.
Safety
• For all installations of electrically heated
products should a residual current circuit
breaker 300 mA for fire protection be used.
• Keeptheareasaroundtheairintake
and exhaust grilles free from possible
obstructions!
• Duringoperationthesurfacesoftheunit
are hot!
• Theunitmustnotbefullyorpartially
covered with clothing, or similar
materials, as overheating can result in a
fire risk!
• Thisapplianceisnotintendedforuse
by persons (including children) with
reduced physical or mental capabilities,
or lack of experience and knowledge,
unless they have been given supervision
or instruction concerning use of the
appliance by a person responsible for
their safety. Children should be supervised
to ensure that they do not play with the
appliance.
Technical data is shown on page 17.

Содержание

Скачать