Programming MCS6, MCS12, MCS16
16
8.6 Restore Memorized Default Settings
The memorized default settings can be restored as follows.
Enter the Program Mode.
Set P-17 to “rSt”.
Exit the Program Mode.
The software version number (e.g. “A12”) appears in the display.
The memorized default settings are restored and the Marine Climate Sys-
tem returns to the Off Mode.
8.7 Programmable Parameters
Programmable Parameters Table
Program
number
Description Default Range
P-1 Operating Mode 0 0 = Automatic mode
1 = Cool only mode
2 = Heat only mode
P-2 High Fan Speed Limit
(arbitrary units)
95 65 – 95
P-3 Low Fan Speed Limit
(arbitrary units)
55 30 – 64
P-4 Compressor Staging
Time Delay
15 5 – 135 s
P-5 Temperature Sensor
Calibration
Ambient
Temperature
Ambient 10 °F
P-6 Failsafe 3 0 = Minimum protection
1 = Continuous, no display
2 = Continuous, with display
3 = Four failures, reset required
P-7 Low AC Voltage Shut-
down (Volts)
115 V OFF
220/230 V – OFF
75 – 105
175 – 205
P-8 De-Icing Cycle 1 OFF
1 = On with 5 °F faceplate sensor
differential
2 = On with 7 °F faceplate sensor
differential
P-9 High Water Tempera-
ture Limit (°F)
OFF 100 – 150