MCS6, MCS12, MCS16 Programming
17
I
NOTE
Should any programming problems or confusion occur, reset the
Memorized Default Settings by entering the program mode and
setting P-17 to “rSt”.
If recent programming changes were made but not saved, the reset
will return to the last saved defaults, which could differ from the
factory defaults.
P-10 Display Brightness
Control
9 4 = Low
13 = Maximum
P-11 Display ºF or ºC F F = Fahrenheit displayed
C = Celsius displayed
P-12 Cycle Pump With
Compressor or
Continuous Pump
OFF OFF = Cycle with compressor
On = Continuous pump
P-13 Reverse Fan Speeds
During Heating Mode
rEF nor = Normal fan operation
rEF = Reversed fan in heating
P-14 Continuous Fan or
Cycle Fan with
Compressor
con CYC = Cycle fan with compressor
con = Continuous fan operation
P-15 Reverse Cycle Heating
or Electric Heat Only
Option Installed (cool-
ing only units)
nor nor = Reverse cycle heating
ELE = Electric heater installed
P-16 Fan Motor type selec-
tion Shaded Pole or
Split Capacitor.
SC SP = Shaded pole fan motor
SC = Split capacitor fan motor
P-17 Reset Memorized
Programming Defaults
nor rSt = Reset defaults
nor = Normal
P-18 Reserved for Future
Option
––
P-19 Reserved for Future
Option
––
P-20 Filter Threshold
(x10 hours)
00 00 – 250
P-21 Current Filter Time
(x10 hours)
x10 Hours Using
Current Filter
P-22 Voltage Calibration
(Volts)
AC Voltage
Program
number
Description Default Range